Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions

Screen 36 – Ground Min, Phase 1-2 Min Demand Currents

36 Gnd Min

____________A

Time

Date

Ph1-2 Min

____________A

Time

Date

 

 

Note: Demand currents are a time integrated value and do not reflect minimum or maximum instantaneous currents. The demand integration time constant is set via the interface software demand metering screen. These are the same values displayed in the histogram screen.

Screen 37 – Phase 3-4 Min, Phase 5-6 Min Currents

37 Ph3-4 Min

____________A

Time

Date

Ph5-6 Min

____________A

Time

Date

 

 

Note: Pressing and holding the RESET TARGETS/RESET MAX CURRENT key for three seconds will reset the minimum and maximum Demand values.

Screen 38 – Fault Location

38 Fault Location

Distance ____________miles

<Control Identification>

TimeDate

Screen 39 – Control Information

39 CPU Firmware

X.XX

Firmware FW Database

X

 

<Control Identification>

Time

Date

 

 

 

 

Screen 40 – Communication Port 2 Settings

This message displays the protocol settings (2179 or DNP3.0), baud rate, and address for Serial Port #2. Baud rate and address are set using the interface soft- ware, while protocol is set at the factory based on user’s specifications.

40 – Comm Port 2

______

Protocol_______

Speed_______

Address_______

Screen 41 – Communication Port 3 Settings

This message displays the protocol settings (2179 or DNP3.0), baud rate, and address for Serial Port #3. Baud rate and address are set using the interface soft- ware, while protocol is set at the factory based on user’s specifications.

41 – Comm Port 3

______

Protocol_______

Speed_______

Address_______

Operation/Indication Pushbuttons

Nine frequently used features are provided on the control operator panel (Figure 7).

Note: These features are activated from the keypad, control interface software or SCADA signal.

To initiate an operation from the operator panel, press the CHANGE/LAMP TEST key to enter the CHANGE mode. The operator has 10 seconds to select an operation and modify settings. If no changes are made, the control will return to its operational state prior to entering the CHANGE mode. This prevents accidental changing of settings.

Red LEDs located on each switch indicate the status of the function, regardless of local or remote activation. For example, if Cold Load Pickup was activated from a SCADA signal, the red indicator would illuminate even though it was not activated from the operator panel.

Note: Operation LEDs activated from local or remote sources do not illuminate when the front panel is in the power- save mode.

GND TRIP

NON

SUPERVISORY

BLOCKED

RECLOSING

BLOCKED

 

 

COLD LOAD

BATTERY

FAST

PICKUP

TEST

TRIPS

BLOCKED

DISABLED

 

ALTERNATE

ALTERNATE

ALTERNATE

PROFILE

PROFILE

PROFILE

NO. 1

NO. 2

NO. 3

Figure 7.

Operation/indication pushbuttons.

GND TRIP BLOCKED

Ground Trip Blocked is activated by pressing the CHANGE/LAMP TEST key, then pressing the GND TRIP BLOCKED key. The red indicator illuminates.

12