Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Screen 36 – Ground Min, Phase
36 Gnd Min | ____________A |
Time | Date |
____________A | |
Time | Date |
|
|
Note: Demand currents are a time integrated value and do not reflect minimum or maximum instantaneous currents. The demand integration time constant is set via the interface software demand metering screen. These are the same values displayed in the histogram screen.
Screen 37 – Phase
37 | ____________A |
Time | Date |
____________A | |
Time | Date |
|
|
Note: Pressing and holding the RESET TARGETS/RESET MAX CURRENT key for three seconds will reset the minimum and maximum Demand values.
Screen 38 – Fault Location
38 Fault Location
Distance ____________miles
<Control Identification>
TimeDate
Screen 39 – Control Information
39 CPU Firmware | X.XX | |
Firmware FW Database | X | |
| <Control Identification> | |
Time | Date |
|
|
|
|
Screen 40 – Communication Port 2 Settings
This message displays the protocol settings (2179 or DNP3.0), baud rate, and address for Serial Port #2. Baud rate and address are set using the interface soft- ware, while protocol is set at the factory based on user’s specifications.
40 – Comm Port 2 | ______ |
Protocol_______
Speed_______
Address_______
Screen 41 – Communication Port 3 Settings
This message displays the protocol settings (2179 or DNP3.0), baud rate, and address for Serial Port #3. Baud rate and address are set using the interface soft- ware, while protocol is set at the factory based on user’s specifications.
41 – Comm Port 3 | ______ |
Protocol_______
Speed_______
Address_______
Operation/Indication Pushbuttons
Nine frequently used features are provided on the control operator panel (Figure 7).
Note: These features are activated from the keypad, control interface software or SCADA signal.
To initiate an operation from the operator panel, press the CHANGE/LAMP TEST key to enter the CHANGE mode. The operator has 10 seconds to select an operation and modify settings. If no changes are made, the control will return to its operational state prior to entering the CHANGE mode. This prevents accidental changing of settings.
Red LEDs located on each switch indicate the status of the function, regardless of local or remote activation. For example, if Cold Load Pickup was activated from a SCADA signal, the red indicator would illuminate even though it was not activated from the operator panel.
Note: Operation LEDs activated from local or remote sources do not illuminate when the front panel is in the power- save mode.
GND TRIP | NON | SUPERVISORY | |
BLOCKED | RECLOSING | BLOCKED | |
|
| ||
COLD LOAD | BATTERY | FAST | |
PICKUP | TEST | TRIPS | |
BLOCKED | DISABLED | ||
| |||
ALTERNATE | ALTERNATE | ALTERNATE | |
PROFILE | PROFILE | PROFILE | |
NO. 1 | NO. 2 | NO. 3 |
Figure 7.
Operation/indication pushbuttons.
GND TRIP BLOCKED
Ground Trip Blocked is activated by pressing the CHANGE/LAMP TEST key, then pressing the GND TRIP BLOCKED key. The red indicator illuminates.
12