Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Grounding with a Remote Supply Voltage Transformer;
Installation of a Form 5 control with a remote supply voltage transformer must include the following:
•Protection of the recloser bushings and the supplying transformer with lightning arresters.
•Grounding of the recloser head and tank.
•Grounding of the transformer tank.
•Grounding of the control cabinet.
•Grounding of the SCADA equipment
IMPORTANT: In
IMPORTANT: All external inputs to the Form 5 control must be routed within 8 inches of their corresponding ground. During a surge, a potential of approximately 1.5kV per foot can develop in the con- ductors. Differences between conductor and ground path lengths can add additional stress to the control components in the event of a power surge.
|
|
| Low Voltage Distribution Network |
| ||
Supply Voltage | Form 5 LS Control | Input | Input |
|
| 115 Vac |
|
|
| Supply Voltage | |||
| Terminal | Terminal |
|
| ||
|
| Form 5 LS Control | ||||
|
|
| ||||
Transformer |
| Block | Block | Local Isolation | ||
AC |
|
| ||||
|
|
|
|
| Transformer | |
| NEUTRAL |
|
| AC |
| Customer |
|
|
|
| NEUTRAL |
| Supplied |
|
|
|
|
|
| Low Voltage |
| External |
|
|
|
| Low Voltage |
| Ground Lug |
| External |
| Arrester | |
|
|
| Ground Lug |
|
| |
ELECTRICAL CONNECTIONS - Remote dedicated |
|
|
|
|
| |
| supply transformer |
| ELECTRICAL CONNECTIONS - using isolation transformer | |||
| Transformer |
| Surge | Surge |
| |
|
| Surge | Arrester |
| ||
|
| Arrester |
| |||
|
| Arrester |
|
|
| |
|
|
|
|
|
| |
|
|
|
|
| Recloser |
|
|
|
|
|
| Head |
|
|
|
|
|
| Ground |
|
| HOT |
|
|
|
|
|
| NEU |
|
|
|
|
|
| GND | Arrester |
|
|
|
|
|
|
|
|
|
| |
|
| Ground |
|
|
|
|
|
|
|
|
| Arrester |
|
|
|
|
|
| Ground | System |
|
|
|
|
|
| Neutral |
| Note: Distance between |
|
| Recloser |
| |
| transformer and |
|
|
|
| |
| recloser should be | Control Cable |
|
| ||
| one pole span or |
|
| |||
|
|
|
|
| ||
| less |
|
|
|
|
|
|
|
|
| Pole |
|
|
| Supply |
| Form 5 LS Control |
| ||
| Voltage |
|
| |||
|
|
|
|
| ||
| Pole |
|
| Input Terminal Block |
| |
| Ground |
|
|
| ||
|
|
| NEU AC |
|
|
|
Pole |
|
|
|
|
|
|
|
|
|
| Customer Ground Connection |
| |
|
|
|
| at External Lug |
|
Figure 30.
Recommended grounding method for the Form 5 Control installed on
36