Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
! | CAUTION: Equipment misoperation. Do not | |
connect this control to an energized recloser | ||
|
until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equip-
ment damage and personal injury. | G110.3 |
Prior to placing the control and recloser into service, the following installation procedures must be properly completed and verified:
1.Control properly mounted for the installation.
2.Recloser installed according to all locally approved
standards and practices.
! | WARNING: Hazardous voltage. Recloser and | |
control must be solidly grounded. Follow all | ||
|
locally approved procedures and safety practices when grounding this equipment. Improper grounding can result in contact with high voltage, which will cause
death or severe personal injury. | G115.1 |
3.Control and recloser properly grounded in accordance with guidelines in this manual.
4.AC power connected to the control. (AC power LED indicator is illuminated.)
5.Control battery connected and tested for proper operation.
6.All control programming entered and verified by appropriate personnel.
7.Control clock set to the correct time.
8.Customer connections for remote and supervisory operation checked and completed in accordance with proper shielding and surge protection.
9.Control cable properly connected and supported.