Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
! | WARNING: Hazardous Voltage. The recloser | |
and control must be solidly grounded. Follow all | ||
|
locally approved procedures and safety practices when grounding this equipment. Improper grounding can result in contact with high voltage, which will cause
death, severe personal injury. | G115.1 |
The control cabinet must be grounded. A grounding connector on the underside of the cabinet will accommodate No. 14 solid through No. 4 stranded conductors.
Suggested methods for grounding the control and recloser are shown in Figures 29, 30, and 31.
Figure 29 illustrates grounding methods for
Figure 30 illustrates grounding methods for
Figure 31 illustrates grounding on a
For effective surge protection all control and power conductors for the Form 5 must be routed parallel to a corresponding ground path. For example, the AC power supply for the control should be parallel to and equal in length to the transformer ground path. The control cable should be parallel to and routed close to the recloser ground path.
34