Standard and UDP Control DIF Module 1
Inputs (cont’d)
| Input | Connector | Function | Description |
|
|
|
|
|
|
|
| 9 | Supervisory | Supervisory | ||
|
|
|
| input by a remote momentary signal. | |
|
|
|
| This input performs the same function as the | |
|
|
|
| key on the operator panel. This input is inactive if the Supervisory | |
|
|
|
| function is disabled. | |
|
|
|
|
|
|
| 10 | Suprv | This input performs the same function as the COLD LOAD | ||
|
|
|
| PICKUP BLOCKED key on the operator panel. This input is inac- | |
|
|
|
| tive if the Supervisory function is disabled. A momentary signal is | |
|
|
|
| required for proper operation. | |
|
|
|
|
|
|
| 11 | Remote Trip and Reclose | Remote Trip and Reclose initiates a trip operation followed by a | ||
|
|
|
| reclose operation. A momentary signal is required for proper | |
|
|
|
| operation. | |
|
|
|
| This input is active with a whetting voltage and causes the control | |
|
|
|
| to perform a trip operation followed by a reclose operation. This | |
|
|
|
| input is active regardless of the state of the Supervisory function. | |
|
|
|
|
|
|
| 12 | Remote Trip and Lockout | Remote Trip and Lockout trips the recloser open and locks out the | ||
|
|
|
| control. It can be used for tripping from external relays and alarms. | |
|
|
|
| A momentary signal is required for proper operation. | |
|
|
|
| This input performs the same function as the TRIP (LOCKOUT) | |
|
|
|
| switch on the operator panel and is active regardless of the state | |
|
|
|
| of the Supervisory function. | |
|
|
|
|
|
|