Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
AUXILIARY POWER FOR
ACCESSORIES
Connection P9 (Figure 18) on the Power Supply module provides 24Vdc (12Vdc is available) to power radio communication units, RTUs and other accessories. The auxiliary power provides 40W peak load capability. Auxiliary power is fused and
Customer 28V connections for auxiliary power are made to terminals 3 and 1 and are continually energized. Terminal 2 and 4 are not used at this time.
|
| P |
|
| |
P |
| 8 |
| ||
| ||
| C | |
| ||
| ||
| ||
| ||
O |
| P |
| ||
|
W U
E
R
S | F1 |
|
|
| |
|
|
| |||
U |
|
|
|
|
|
P | SW |
|
|
| P |
P | 28V |
|
|
| 9 |
|
|
| U | ||
L | SW (+) 2 |
|
|
| |
|
|
|
| A | |
Y | 28V (+) 1 |
|
|
| X |
|
|
|
|
Figure 18.
Power Supply Module Connection P9 provides 24Vdc power to radio communication units.
RECLOSER INTERFACE (RIF) MODULE CONFIGURATION
The Recloser Interface (RIF) Module is
CAUTION: Equipment damage. Always wear a grounding wrist strap to control static electricity before handling circuit boards. Failure to use this strap may result in cir-
cuit board damage. | T253.1 |
IMPORTANT: The Form 5 control must be completely
To remove the RIF Module for configuration:
1.Disconnect the control battery.
2.Remove the four connectors from the front of the RIF Module.
3.Remove the nut and disconnect the grounding strap to the operator panel. See Figure 4.
4.Disconnect the wiring harness connectors from the bottom of the RIF Module.
Note: Press the locking tabs to release the harness con- nectors.
5.Remove the four 11mm (.437 in) screws securing the board to the mounting bracket.
6.Pull the module out of the cabinet.
The dip switches are located on the side of the module.
7.Configure the RIF board as shown in Figure 19.
8.After configuration, place the module back into posi- tion in the control cabinet and secure to the mounting bracket with screws previously removed.
9.Replace nut securing the RIF Module grounding strap
10.Replace all connectors on the front and bottom of the RIF Module.
Example shown for 120Vac operation:
SENSOR |
|
|
VOLTAGE | POLE1 | POLE2 |
|
|
|
12Vac | OFF | OFF |
120Vac* | OFF | ON |
240Vac | ON | ON |
|
|
|
*120Vac is
INPUT VOLTAGE
SELECTION
OFF | ON | ||||
BUSHING 2 (XØ) |
|
|
|
| POLE 1 |
|
|
|
| ||
|
|
|
|
| POLE 2 |
BUSHING 4 (YØ) |
|
|
|
| POLE 1 |
|
|
|
| POLE 2 | |
|
|
|
| ||
BUSHING 6 (ZØ) |
|
|
|
| POLE 1 |
|
|
|
| ||
|
|
|
| ||
|
|
|
|
| POLE 2 |
| S7 |
|
| ||
| S7 |
|
|
INPUT VOLTAGE | |||||
SELECTION | |||||
OFF | ON | ||||
BUSHING 1 (AØ) |
|
|
|
| POLE 1 |
|
|
|
| ||
|
|
|
|
| POLE 2 |
BUSHING 3 (BØ) |
|
|
|
| POLE 1 |
|
|
|
| POLE 2 | |
|
|
|
| ||
BUSHING 5 (CØ) |
|
|
|
| POLE 1 |
|
|
|
| ||
|
|
|
| ||
|
|
|
|
| POLE 2 |
|
|
|
|
|
|
S8 |
|
|
Figure 19.
Recloser Interface (RIF) Module indicates the factory
20