DISCRETE INTERFACE (DIF)
ACCESSORY
The Discrete Interface (DIF) module accessory (Figure
25)permits connection of
IMPORTANT: Do not use DIF module for overcurrent protection. Digital SCADA can be used for this applica- tion. The control gives priority to TCC timing and issuing a trip signal rather than changing the status of a DIF output or responding to a DIF input.
The DIF module contains 12
Whetting voltage for the DIF inputs can be supplied by the DIF module or by the customer as shown in Figure 26.
Note: 28 Vdc (nominal) is provided from the DIF module via connector P5 for use as whetting voltage for inputs to P4. As an alternative, the user can supply whetting voltage from an auxiliary source, such as a RTU.
The input voltage range is 12 to 120 Vac or Vdc. The 12 outputs are Form C relay contacts. Six of the module outputs are latching and the other six are
Note: Latching is defined as an output that retains its status when control power is removed.
Note: A remote function is not controlled by the SUPERVISORY BLOCKED switch.
Customer Connection
Information
! | CAUTION: Equipment damage. Do not drill con- | |
nection holes into the top of the cabinet. Connec- | ||
|
tion holes in the top of the cabinet will allow moisture to seep into the control and damage the components or cause control misoperation. Failure to comply will void
! | CAUTION: Equipment damage; misoperation. | |
External leads must be shielded and the shield | ||
|
must be grounded at both ends. Terminate each lead with a 320 Vac, 160 Joules metal oxide varistor (MOV), or equivalent, at the remote end. Attach MOVs between the leads and ground. Failure to properly shield and protect leads can result in equipment damage and/or
| unintentional operation. |
|
|
|
|
|
|
| G117.3 | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| INPUT COMMON |
|
|
|
|
|
|
|
| |||
|
|
| 4 |
|
|
|
|
|
| |||||
|
|
|
| 28V | 3 |
|
|
|
|
| P5 | |||
|
|
|
| 28V (+) |
|
|
|
|
| |||||
|
|
|
| 2 |
|
|
|
|
| |||||
|
|
|
|
|
|
|
| |||||||
|
|
| OUTPUT COMMON |
|
|
|
|
| WHETTING | |||||
|
|
| 1 |
|
|
|
|
| ||||||
|
|
|
|
|
|
|
| VOLTAGE | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 6 | 12 |
|
|
|
|
|
| |||
|
|
|
| 11 |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| 5 | 10 |
|
|
|
|
|
| |||
|
|
|
| 9 |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| 4 | 8 |
|
|
|
|
|
| |||
|
|
|
| 7 |
|
|
|
|
| P3 | ||||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| 3 | 6 |
|
|
|
|
| ||||
|
|
|
| 5 |
|
|
|
|
| UNLATCHED | ||||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| DISCRETE |
| 2 | 4 |
|
|
|
|
| OUTPUTS | |||
|
|
| 3 |
|
|
|
|
|
| |||||
|
| INTERFACE |
|
|
|
|
|
|
|
|
|
| ||
|
|
| 1 | 2 |
|
|
|
|
|
| ||||
|
| MODULE |
| 1 |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| ACCESSORY |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 12 | 12 |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| 11 |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| 10 |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| 11 |
|
|
|
|
|
| ||
|
|
|
|
|
| 9 |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| 8 |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| 10 |
|
|
|
|
| P2 | ||
|
|
|
|
|
| 7 |
|
|
|
|
| |||
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
| 6 |
|
|
|
|
| LATCHED | |
|
|
|
|
|
| 9 | 5 |
|
|
|
|
| OUTPUTS | |
|
|
|
|
|
|
| 4 |
|
|
|
|
|
| |
|
|
|
|
|
| 8 | 3 |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| 2 |
|
|
|
|
|
| |
|
|
|
|
|
| 7 | 1 |
|
|
|
|
|
| |
|
|
| 12 |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| 11 |
|
| 12 |
|
|
|
|
|
| ||
|
|
|
|
| 11 |
|
|
|
|
|
| |||
|
|
| 10 |
|
|
|
|
|
|
|
| |||
|
|
|
|
| 10 |
|
|
|
|
|
| |||
|
|
| 9 |
|
|
|
|
|
|
|
| |||
|
|
|
|
| 9 |
|
|
|
|
|
| |||
|
|
| 8 |
|
|
|
|
|
|
|
| |||
|
|
|
|
| 8 |
|
|
|
|
|
| |||
|
|
| 7 |
|
|
|
|
|
|
|
| |||
|
|
|
|
| 7 |
|
|
|
|
| P4 | |||
|
|
| 6 |
|
|
|
|
|
|
| ||||
|
|
|
|
| 6 |
|
|
|
|
| ||||
|
|
| 5 |
|
|
|
|
|
|
| INPUTS | |||
|
|
|
|
| 5 |
|
|
|
|
| ||||
|
|
| 4 |
|
|
|
|
|
|
| (12 TO 120 | |||
|
|
|
|
| 4 |
|
|
|
|
| ||||
|
|
| 3 |
|
|
|
|
|
|
| VAC OR VDC) | |||
|
|
|
|
| 3 |
|
|
|
|
| ||||
|
|
| 2 |
|
|
|
|
|
|
| WHETTING | |||
|
|
|
|
| 2 |
|
|
|
|
| ||||
|
|
| 1 |
|
|
|
|
|
|
| VOLTAGE | |||
|
|
|
|
| 1 |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 25.
Discrete Interface (DIF) Module.
P5
INPUT COMMON
4
the control’s factory warranty. | T249.0 |
28V
28V (+)
3
Figure 25 shows the
Figure 27 shows customer connections to the DIF outputs at P2 and P3.
2
OUTPUT COMMONCustomer-Supplied
1
Wiring for Whetting Voltage
Note: Wiring to | REMOTE | ||||
CONTACTS | |||||
reversed if necessary. |
|
|
|
|
|
To P4
Inputs 1 thru 12
Figure 26.
Customer connections for supplying whetting voltage to DIF inputs.
23