The Form 5 control operator panel (Figure 8) allows local operation and status interrogation through
All indicators with the exception of Hot Line Tag and recloser status are automatically turned off after 5 minutes of operator panel inactivity.
Reactivating is accomplished by pressing any operation switch. The LCD messages will remain while in this
CONTROL OK
AC POWER
ABOVE MIN TRIP
CHECK BATTERY
RECLOSER MALFUNCTION
REVERSE POWER FLOW
BUSHINGS | BACK | NEXT | |
BUSHINGS | RESET | CHANGE | |
| TARGETS |
| |
BUSHINGS | RESET | LAMP | |
MAX CURRENT | TEST |
GROUND FAULT TARGET |
|
|
|
| |
GND TRIP | NON | SUPERVISORY | |||
|
| BLOCKED | RECLOSING | BLOCKED | |
BUSHINGS | COLD LOAD | BATTERY | FAST | ||
|
| PICK UP | TEST | TRIPS | |
|
| BLOCKED | DISABLED | ||
BUSHINGS |
| ||||
|
|
|
| ||
BUSHINGS | ALTERNATE | ALTERNATE | ALTERNATE | ||
|
| PROFILE | PROFILE | PROFILE | |
|
| NO. 1 | NO. 2 | NO. 3 | |
|
| TX 3 | TX 2 |
|
|
RECLOSER CLOSED HOT LINE |
|
|
| ||
RECLOSER OPEN | TAG | ON |
|
|
|
|
| RS232 | |||
|
|
|
| ||
CONTROL LOCKOUT | OFF RX 3 | RX 2 |
|
| |
TRIP | CLOSE | KYLE | ® |
(LOCKOUT)
FORM 5
RECLOSER CONTROL
Figure 5.
Form 5 control operator panel.
LED Indicators
The operator panel LED indicators (Figure 5) give instant information on the control and recloser status.
LED indicators include:
CONTROL OK
This green LED is illuminated when the continuous self- diagnostics of the control have detected no CPU or memory malfunctions and indicate that the control is capable of normal operation.
AC POWER
This green LED is illuminated when the presence of ac input power to the control is sensed. The LED will turn off if ac power is lost for more than 10 seconds.
ABOVE MIN TRIP
This red LED is illuminated when the control detects that current is above the programmed minimum trip value for Bushings
CHECK BATTERY
This red indicator illuminates for two conditions:
1.Battery voltage is below 20 Vdc or drops 2Vdc or more during battery test.
2.The control fails a manual battery test. The LED will remain on until a successful battery test is completed.
Refer to the Battery Test Procedure in this manual for more information.
RECLOSER MALFUNCTION
This red indicator is illuminated when the control detects a failure in a trip or close operation. It turns off automatically if the recloser returns to the proper state.
REVERSE POWER FLOW
This red indicator illuminates when the control detects power flow from the load side to the source side of the recloser.
Note: Voltage sensor polarity and phase must be correct for reverse power flow to function properly.
BUSHINGS
BUSHINGS
BUSHINGS
GROUND FAULT TARGET
SENSITIVE GROUND FAULT TARGET
These red target LEDs illuminate when the control issues an overcurrent trip signal while the respective phase current or ground current exceeds the minimum pickup value. Reset is accomplished automatically when Auto Reset is activated and a successful close operation is performed or manual reset is accomplished by pressing the RESET TARGETS button on the control operator panel.
BUSHINGS
BUSHINGS
BUSHINGS
These red voltage LEDs illuminate when the control detects the presence of voltage on the respective bushings as connected to TB1. Refer to the Customer Connections for AC Power section in these instructions to determine the appropriate power connections.
RECLOSER CLOSED
This red indicator is illuminated when the control senses that the recloser mechanism is in the closed position.