Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
The standard Form 5 control is equipped with a operator panel
If a
Note: The operator panel
The condition of the control battery is tested by depressing the BATTERY TEST hot key on the operator panel. No external current/voltage meter is necessary for testing.
The control performs a
To perform a battery test:
1.Using the Next and BACK keys, scroll through the LCD display to Screen 31, the Battery Monitor screen.
2.Record the NORMAL VOLTS and NORMAL CUR- RENT readings from the screen.
Note: Voltage should be between 25 to 31 volts with higher readings at colder temperatures. Under nor- mal conditions with ac connected and the battery trickle charging, the current should read less than 20 mA. With ac connected and in bulk charging mode, current will range from 12 to 600 mA. With ac disconnected and the battery supplying the load, current will read
3.Momentarily, press the CHANGE/LAMP TEST key, then BATTERY TEST key.
Note: AC power can be either connected or disconnected for Step 3.
4.Record the TEST VOLTS reading from the LCD and the status of the CHECK BATTERY LED. Service the battery if the CHECK BATTERY LED is illuminated.
The Form 5 recloser control offers numerous standard features and accessories that allow the user the utmost flexibility in designing a control suitable for their application requirements.
Under/Over Frequency Loadshedding
The Form 5 control includes provisions for frequency loadshedding that trips the recloser for conditions of under or over system frequency. Access to this feature is through frequency threshold, trip time, and allowable voltage threshold.
With the
A frequency alarm is available and can be configured for notification.
Voltage Protection (120
Voltage protection functionality is included as standard on all Form 5 controls. A recloser trip will be issued for under and over voltage conditions when the monitored voltage falls outside
Protection Profiles
Four separate protection profiles are included to allow the user to adapt overcurrent settings for varying system conditions such as load, live line work or weather. The active profile is selected from the operator panel or with the interface software or SCADA (Figure 9). Each profile has 14 TCC specifications plus reclose intervals, sequence coordination and reset times to maintain independent protection parameters.
Figure 9.
Interface software sample protection profile.
14