Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions

Standard and UDP Control DIF Module 1

Inputs

The DIF inputs are factory-configured as momentary (0.25 sec. duration) or maintained functions. Supervisory signals do not have any effect when supervisory blocked is active. Remote inputs function when supervisory is blocked.

 

 

Input

Connector

Function

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

1

P4-1

Supervisory Trip and Lockout

Supervisory Trip and Lockout trips the recloser open and locks out

 

 

 

 

 

 

the control. The control remains locked out until closed manually or

 

 

 

 

 

 

by the supervisory close feature. A momentary signal is required.

 

 

 

 

 

 

 

 

 

 

 

2

P4-2

Supervisory Close

Supervisory Close initiates a closing signal to the recloser. A

 

 

 

 

 

 

momentary signal is required for proper operation.

 

 

 

 

 

 

 

 

 

 

 

3

P4-3

Remote Hot Line Tag

Remote Hot Line Tag performs the same functions as the HOT

 

 

 

 

 

 

LINE TAG switch on the operator panel. Remote Hot line Tag is

 

 

 

 

 

 

activated by a maintained SCADA command, a serial command,

 

 

 

 

 

 

or locally via a operator panel switch. This input is active regardless

 

 

 

 

 

 

of the state of the supervisory function.

 

 

 

 

 

 

 

 

 

 

 

4

P4-4

Supervisory Ground Trip Block

Supervisory Ground Trip Block provides supervisory operation of

 

 

 

 

 

 

ground trip block by a remote momentary signal.

 

 

 

 

 

 

This input performs the same function as the GND TRIP BLOCKED

 

 

 

 

 

 

key on the operator panel. This input is inactive if the Supervisory

 

 

 

 

 

 

function is disabled.

 

 

 

 

 

 

 

 

 

 

 

5

P4-5

Supervisory Alternate Profile 1

 

 

 

 

 

 

Supervisory Alternate Profiles provides selection of alternate pro-

 

 

6

P4-6

Supervisory Alternate Profile 2

 

grammed values for phase and ground. This feature is activated by

 

 

 

7

P4-7

Supervisory Alternate Profile 3*

 

a remote momentary signal.

 

 

 

 

 

 

 

 

These inputs are active with a momentary whetting voltage and

 

 

 

 

 

 

 

 

cause the control to select the respective Supervisory Alternate Pro-

 

 

 

 

 

 

 

 

file. The inputs are inactive if the Supervisory function is disabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

P4-8

Supervisory Normal Profile

Supervisory Normal Profile requires a momentary signal for proper

 

 

 

 

 

 

operation.

 

 

 

 

 

 

This input is active with a whetting voltage and causes the control

 

 

 

 

 

 

to select Normal Protection Profile. This input is inactive if the

 

 

 

 

 

 

Supervisory function is disabled.

 

 

 

 

 

 

 

 

 

 

Note: Supervisory Alternate Profile 3 replaced by Switch

Mode on UDP controls.