Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions

Form 5 Control Default Test Optimal Values

6.

Trip Sequence

 

1st

2nd

3rd

4th

Ground Timing

Normal

Ground 2X

0.214

0.212

3.894

3.896

 

 

 

Ground 5X

0.012

0.016

1.097

1.099

 

 

 

Ground 10X

0.008

0.014

0.652

0.653

 

 

Profile #1

Ground 2X

0.214

0.212

3.894

3.896

 

 

 

Ground 5X

0.012

0.016

0.952*

0.954*

 

 

 

Ground 10X

0.008

0.014

0.280*

0.276*

 

 

Profile #2

Ground 2X

0.214

0.212

3.984

3.896

 

 

 

Ground 5X

0.012

0.016

0.952*

0.954*

 

 

 

Ground 10X

0.008

0.014

0.280*

0.276*

 

 

Profile #3

Ground 2X

0.214

0.212

3.894

3.896

 

 

 

Ground 5X

0.012

0.016

0.952*

0.954*

 

 

 

Ground 10X

0.008

0.014

0.280*

0.276*

 

7.

Enabled

Phase 2X

0.153

lockout

lockout

lockout

Non-Reclose

Disabled

Phase 2X

0.152

0.153

1.420

1.433

 

8. Cold Load

Block Off

Phase 2X

1.420

1.433

lockout

lockout

PickUp Blocked

Block On

 

0.158

0.154

1.420

1.433

 

 

 

 

 

 

 

 

9. Fast Trips

Enabled

Phase 2X

1.419

1.422

lockout

lockout

 

Disabled

Phase 2X

0.155

0.156

1.418

1.424

 

10.

No Reclose

Phase 2X

0.014

lockout

lockout

lockout

Hot Line Tag

Enabled

Phase 2X

0.155

0.156

1.148

1.424

 

11.

Reclose Sequence

1st

2nd

3rd

4th

Test Reclose

Reclose Times

1.975

1.974

4.968

lockout

12.

Fuse Out

Can’t Close?

Yes

No

 

 

 

Close Circuit

 

 

 

XXX

 

 

 

Disable Fuse

Fuse In

Can Close?

Yes

No

 

 

 

 

 

 

XXX

 

 

 

 

13. Instantaneous

Phase A

Phase B

 

Phase C

 

 

Demand Metering

Amps 80

Amps 81

 

 

Amps 80

 

 

 

 

 

 

 

 

 

 

*Refer to the Test Ground Timing section of this manual.