Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Form 5 Control Default Test Optimal Values
6. | Trip Sequence |
| 1st | 2nd | 3rd | 4th | |
Ground Timing | Normal | Ground 2X | 0.214 | 0.212 | 3.894 | 3.896 |
|
|
| Ground 5X | 0.012 | 0.016 | 1.097 | 1.099 |
|
|
| Ground 10X | 0.008 | 0.014 | 0.652 | 0.653 |
|
| Profile #1 | Ground 2X | 0.214 | 0.212 | 3.894 | 3.896 |
|
|
| Ground 5X | 0.012 | 0.016 | 0.952* | 0.954* |
|
|
| Ground 10X | 0.008 | 0.014 | 0.280* | 0.276* |
|
| Profile #2 | Ground 2X | 0.214 | 0.212 | 3.984 | 3.896 |
|
|
| Ground 5X | 0.012 | 0.016 | 0.952* | 0.954* |
|
|
| Ground 10X | 0.008 | 0.014 | 0.280* | 0.276* |
|
| Profile #3 | Ground 2X | 0.214 | 0.212 | 3.894 | 3.896 |
|
|
| Ground 5X | 0.012 | 0.016 | 0.952* | 0.954* |
|
|
| Ground 10X | 0.008 | 0.014 | 0.280* | 0.276* |
|
7. | Enabled | Phase 2X | 0.153 | lockout | lockout | lockout | |
Disabled | Phase 2X | 0.152 | 0.153 | 1.420 | 1.433 |
| |
8. Cold Load | Block Off | Phase 2X | 1.420 | 1.433 | lockout | lockout | |
PickUp Blocked | Block On |
| 0.158 | 0.154 | 1.420 | 1.433 |
|
|
|
|
|
|
|
| |
9. Fast Trips | Enabled | Phase 2X | 1.419 | 1.422 | lockout | lockout | |
| Disabled | Phase 2X | 0.155 | 0.156 | 1.418 | 1.424 |
|
10. | No Reclose | Phase 2X | 0.014 | lockout | lockout | lockout | |
Hot Line Tag | Enabled | Phase 2X | 0.155 | 0.156 | 1.148 | 1.424 |
|
11. | Reclose Sequence | 1st | 2nd | 3rd | 4th | ||
Test Reclose | Reclose Times | 1.975 | 1.974 | 4.968 | lockout | ||
12. | Fuse Out | Can’t Close? | Yes | No |
|
|
|
Close Circuit |
|
|
| XXX |
|
|
|
Disable Fuse | Fuse In | Can Close? | Yes | No |
|
|
|
|
|
| XXX |
|
|
|
|
13. Instantaneous | Phase A | Phase B |
| Phase C |
|
| |
Demand Metering | Amps 80 | Amps 81 |
|
| Amps 80 |
|
|
|
|
|
|
|
|
|
|
*Refer to the Test Ground Timing section of this manual.
52