Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Manual
! | WARNING: Explosion Hazard. Excessive Con- | |
tact Arcing. Do not use the manual closing tool to | ||
|
close an
equipment damage. | T203.2 |
If
To manually close the recloser:
1.Remove the closing tool port cover and gasket from the side of the recloser head casting.
2.Insert the
CAUTION: Equipment damage. Do not turn the manual closing tool more than
the pin on the closing shaft of the recloser. | T222.0 |
3.Close the recloser by placing the yellow operating handle (located under the sleethood) into the up or CLOSED position and turning the closing tool one-
quarter turn clockwise.
4.After each trip operation, about 1/2 second elapses while the closing solenoid plunger is moving upward to reset the main toggle latch.
5.After the main toggle latch resets, the recloser can be closed again by operating the manual closing tool.
6.Replace the gasket and port cover on the recloser head after testing has been completed.
Figure 46.
Using a manual closing tool to operate the recloser.