TESTING AND TROUBLESHOOTING
! | CAUTION: Equipment misoperation. Do not | |
connect this control to an energized recloser | ||
|
until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equip-
ment damage and personal injury. | G110.3 |
IMPORTANT: The Form 5 recloser control can be taken out of service for testing and placed back into service without
Testing an Installed Control
The following tests to determine initial operation of the Form 5 control can be performed while connected to an operating recloser. These are the only tests performed on an installed, operating control. All other tests described in this Testing and Troubleshooting section require the Form 5 control to be removed from service, connected to a bypassed recloser, or tested at a location where the proper testing equipment is available.
1.
2.Scroll through the LCD display messages as described in the LCD Display Messages section of these instructions. Refer to Form 5 Control operator panel section of this manual.
Check the operational values for currents, voltages, and other metering information.
3.Check that the LED for AC power is illuminated on the control operator panel. This indicates the presence of AC power.
4.Test battery operation, using the procedures described in the Battery Test Procedure section of these instructions.
Check CPU Status
Check the operating status of the CPU module. Open the cabinet door and locate the LED indicator (Figure 40).
The LED indicator on the CPU module should flash at a rate of one flash per second for normal 60 Hz operation (slightly faster for 50Hz).
Testing With Type MET Tester
The Kyle Type MET Electronic Recloser Control Tester (Figure 41) is used for testing the Form 5 control.
The MET Tester is completely
CPU Module LED Indicator
CPU Module
(Central Processing Unit)
Figure 40. | 99002KM |
| |
Form 5 control CPU module. |
|
|
|
|
|
of all operating parameters. Refer to Service Information
IMPORTANT: The Form 5 DC NOVA control cannot be tested with the standard Kyle MET Tester. A junction box accessory for the MET tester is available for testing the Form 5 DC NOVA control.
IMPORTANT: When the control is open and current is present, the Trip Fail detection circuit in the Form 5 control will activate when the Kyle Type MET tester CALIBRATE switch is ON. Depress and hold the RESET TARGET keypad on the control for 3 seconds to reset the condition.
Figure 41. | 010028KM |
| |
Kyle Type MET electronic recloser control tester. | |
|
|
43