Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions

Standard and UDP Control DIF Module 1

Outputs

The 12 outputs of the DIF Module are Form C relay contacts. Six of the outputs are latching and six are non-latching.

Note: Contacts shown in inactive mode.

 

 

Output

Connector

Function

Type

 

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

P3-1 NC

Normal Profile

Non-Latched

 

 

 

 

 

 

 

 

 

 

 

 

Normal Profile is active only when Alternate Profiles are

 

 

 

 

 

P3-2 NO

 

 

 

 

inactive. Normal reclosing operations will follow.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

P3-3 NC

Non-Reclosing

Non-Latched

 

 

 

 

 

 

 

 

 

 

 

 

 

This output is active when the NON-RECLOSING indicator

 

 

 

 

 

P3-4 NO

 

 

 

 

 

in the operator panel is illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

P3-5 NC

Cold-Load Pickup Blocked

Non-Latched

 

 

 

 

 

 

 

 

 

 

 

This output is active when the COLD LOAD PICKUP

 

 

 

 

 

P3-6 NO

 

 

 

BLOCKED indicator on the operator panel is illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

P3-7 NC

Supervisory Blocked

Non-Latched

 

 

 

 

 

 

 

 

 

 

Supervisory Blocked prevents operation from supervisory

 

 

 

 

 

P3-8 NO

 

 

 

control. Programming is accessible from the operator panel.

 

 

 

 

 

 

 

 

 

 

This output is active when the SUPERVISORY BLOCKED

 

 

 

 

 

 

 

 

 

 

indicator on the operator panel is illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

P3-9 NC

AC power

Non-Latched

 

 

 

 

 

 

 

 

 

 

 

AC power indicator is active when the control detects the

 

 

 

 

 

P3-10 NO

 

 

 

presence of AC power. This output is active when the AC

 

 

 

 

 

 

 

 

 

 

power indicator on the operator panel is illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

P3-11 NC

Control OK

Non-Latched

 

 

 

 

 

 

 

 

 

Control OK indicator is active when the control is able to per-

 

 

 

 

 

P3-12 NO

 

 

 

form protection operations. This output is active when the

 

 

 

 

 

 

 

 

 

 

CONTROL OK indicator on the operator panel is illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

P2-1 NO

Recloser Open

Latched

 

 

 

 

 

 

 

 

 

 

 

Recloser Open indicator is active when the recloser signals

 

 

 

 

 

P2-2 NC

 

 

 

the control that the recloser contacts are open. This output is

 

 

 

 

 

 

 

 

 

 

active when the RECLOSER OPEN indicator is illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

P2-3 NO

Hot Line Tag

Latched

 

 

 

 

 

 

 

 

 

 

 

 

With Hot Line Tag active, close circuit is disabled and the

 

 

 

 

 

P2-4 NC

 

 

 

HOT LINE TAG indicator is illuminated. With Hot Line Tag

 

 

 

 

 

 

 

 

 

 

inactive, the control switched back to the previous time cur-

 

 

 

 

 

 

 

 

 

 

rent curve for the active profile, close circuit is enabled and

 

 

 

 

 

 

 

 

 

 

the HOT LINE TAG indicator is off. This output is active

 

 

 

 

 

 

 

 

 

 

when the operator panel indicator is illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

P2-5 NO

Ground Trip Blocked

Latched

 

 

 

 

 

 

 

 

 

 

 

 

Ground Trip Blocked causes the control to block ground trip-

 

 

 

 

 

P2-6 NC

 

 

 

ping operations. This output is active when the GND TRIP

 

 

 

 

 

 

 

 

 

 

BLOCKED INDICATOR on the operator panel is illuminated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

P2-7 NO

Alternate Profile 1

Latched

 

 

 

 

 

 

 

 

 

 

 

 

These outputs are active when the respective ALTERNATE

 

 

 

 

 

P2-8 NC

 

 

 

PROFILE indicators on the operator panel is illuminated.

 

 

 

 

11

P2-9 NO

Alternate Profile 2

Latched

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2-10 NC

 

 

 

 

 

 

 

 

 

 

 

 

 

12

P2-11 NO

Alternate Profile 3*

Latched

 

 

 

 

 

 

 

 

 

 

 

 

 

P2-12 NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Note: Supervisory Alternate Profile 3 replaced by Switch Mode on UDP controls.

28