INPUT ACCURACY
Sensed Currents
Note: Control only, does not include sensor tolerance, but does include the phase current summing process.
Phase
Range: 1 A to 10,000 A for 500:1 CTs 2 A to 20,000 A for 1000:1 CTs 4 A to 40,000 A for 2000:1 CTs
Accuracy:± 1 mA from 10 mA to 125 mA 0.8% from 125 mA to 1600 mA
(Control only, does not include sensor tolerance.)
Ground
Sensed Source Voltages
Voltage measurement accuracy:
±0.4V from 5V to 80V
0.5% from 80V to 135V
Range: 1 A to 5,000 A for 500:1 CTs 2 A to 10,000 A for 1000:1 CTs 4 A to 20,000 A for 2000:1 CTs
Accuracy: ± 3 mA from 10 mA to 125 mA 2.4% from 125 mA to 1600 mA