SAFETY FOR LIFE
Grounding with a Local Supply Voltage Transformer;
Installation of a Form 5 control with a local supply voltage transformer must include the following:
•Protection of the recloser bushings and the supplying transformer with lightning arresters.
•Grounding of the recloser head and tank.
•Grounding of the transformer tank.
•Grounding of the control cabinet.
•Grounding of the SCADA equipment.
IMPORTANT: All external inputs to the Form 5 control must be routed within 8 inches of their corresponding ground. During a surge, a potential of approximately
1.5kV per foot can develop in the conductors. Differ- ences between conductor and ground path lengths can add additional stress to the control components in the event of a power surge.
IMPORTANT: In
The use of a grounding mat may be required depending upon the local safety regulations defining the permissible step and touch potential levels. Consult local regulations for proper grounding procedures.
Surge
TransformerArrester
Surge
Arrester
AC
NEU
GND
Supply
Voltage
Control
Cable
Pole
Ground
AC
NEU
| Surge | Supply Voltage |
| |
| Arrester |
| ||
|
| Form 5 LS Control | Input Terminal | |
|
|
| ||
|
| Transformer | Block | |
|
|
| ||
|
|
| AC |
|
| Recloser |
| NEUTRAL |
|
| Head Ground |
|
|
|
|
|
| External | |
|
|
| Ground Lug | |
Arrester Ground |
| ELECTRICAL CONNECTIONS |
| |
|
|
| Line to Neutral connected transformer |
|
Recloser |
| Supply Voltage | ||
|
|
| Form 5 LS Control |
|
|
|
| Transformer | Line |
|
|
| AC | |
Pole |
|
| to | |
|
|
| NEUTRAL | Line |
|
|
|
| Voltage |
Form 5 LS |
|
|
| |
Control | Input Terminal |
|
| |
|
| Block | External |
|
Input |
|
| Ground Lug |
|
Terminal |
|
|
|
|
Block | ELECTRICAL CONNECTIONS | |
Line to Line connected transformer | ||
| ||
Customer Ground Connection |
| |
At External Lug |
|
Figure 29.
Recommended grounding method for the Form 5 Control installed on
35