System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
5-90 Section 5. Installing a Raptor Level Gauging System
5.10 INSTALLING A ROSEMOUNT 5300
The Rosemount 5300 Guided Wave Radar is most conveniently installed in
TankMaster WinSetup by utilizing the integrated option included as part of the
Rosemount 2410 Tank Hub installation procedure. In a following step, the
5300 is configured via the 5300 GWR window, see “Configuration via 5300
Properties” on page 5-91. The 5300 GWR window includes tabs for basic and
advanced configuration of a Rosemount 5300.
When adding a Rosemount 5300 to a Rosemount 2410 in an existing Raptor
system, the 5300 needs to be mapped to the appropriate tank in the 2410
tank database. Configuration is performed via the 5300 GWR window. See
“Adding a Tank to a Raptor System” on page5-114 for further information.
A Rosemount 5300 is most conveniently installed by utilizing the integrated
option included as part of the Rosemount 2410 Tank Hub installation
procedure.
The 5300 can also be installed and configured by using the WinSetup
installation Wizard (see “Installing a 5300 Using the Installation Wizard” on
page 5-95). This method should only be used in exceptional cases when, for
example, the 5300 is connected to the Tankbus at a later stage and not
available when installing the 2410 Tank Hub.
The following configuration steps are included in the basic configuration of a
Rosemount 5300 Guided Wave Radar:
communication parameters
•probe type
tank geometry
Due to the properties of the product, the shape of the tank, or other
circumstances, further configuration may be needed in addition to the basic
configuration. Disturbing objects and turbulent conditions in the tank may also
require advanced measures to be taken. The TankMaster WinSetup
configuration tool includes advanced options for the 5300 such as:
tank environmental conditions
See “Advanced Configuration” on page 5-99 for further information on
advanced configuration options.
For further information on installation and configuration of a Rosemount 5300
Guided Wave Radar see the Rosemount 5300 Reference Manual (Document