System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
5-26 Section 5. Installing a Raptor Level Gauging System
3. FCU 2160 communication setup.
Choose the communication protocol channel which is associated with
the TankMaster workstation communication port that is connected to the
2160 FCU.
To check which channels are enabled:
a. in the WinSetup workspace open the Protocols folder
b. click the right mous e button on the ModbusMaster protocol icon
c. choose the Properties option
To check which communication port that is associated with a certain
channel:
a. right-click the protocol channe l icon
b. open the Communication tab and check which communication port
that is selected
See chapter “Master Protocol Channel Configuration” on page 5-7 for
more information on how to configure communication protocols.
The 2160 FCU can be connected to a TankMaster PC via a Rosemount
2180 Field Bus Modem, or directly using the RS232 interface, see
“Communication Protocol Setup” on page 5-6.
4. To verify communication with the 2160 FCU, enter the Field
Communication Unit’s Modbus Address and click the Verify
Communication button. The Unit Id will appear if the correct Modbus
Address was entered (the 2160 is shipped with the default Modbus
address=245).
In case you would like to change the current Modbus address, or the
address is unknown, click the Change Address on Device button.