System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
5-106 Section 5. Installing a Raptor Level Gauging System
8. Configure the tank.
The Tank Configuration window lets you enable tank measurement variables
such as Vapor Temperature, Vapor Pressure, Liquid Pressure, and Free
Water Level (FWL) to be used for calculations of Observed Density and
other inventory parameters. See the Tan kM ast er WinOpi Reference Manual
for more information on inventory parameters.
The Calculate in TankMaster check box may be used for devices without
internal calculation of Level Rate. By selecting this check box the Level Rate
is calculated by the TankMaster program.
Liquid Pressure and Vapor Pressure are not automatically mapped to
measurement instruments. These measurement variables have to be mapped
to an instrument in the 22XX ATD/Advanced ParameterSource Configuration
window in order to make them available for configuration in the
TankConfiguration window. See Figure 5-11 on page 5-107 for an example of
how to map the Liquid Pressure variable to the output of a Rosemount 3051S
pressure transmitter.
See also “Advanced Parameter Source Configuration” on page 5-74 for
further information on mapping tank measurement variables to source
devices.
To open the 22XX ATD/Advanced Parameter Source Configuration window:
a. In the TankMaster WinSetup workspace, click the right mouse
button on the ATD device icon and choose the Properties option.
b. Select the Advanced Parameter Source Configuration tab.
c. Map the appropriate tank measurement variable to the output of a
transmitter that is available on the Tankbus. See an example in
Figure 5-11 on page5-107.