Manual Supplement
Rosemount 5300/5400 Series
To change the Modbus address and communication parameters in Rosemount Radar Master (RRM):
1.Start RRM and connect to the transmitter.
2.In RRM, select Setup>General.
Modbus Setup
3.Select the Communication tab.
4.Click the Modbus Setup button.
5.In the Modbus Setup window, select Modbus protocol and type the desired Modbus address.
6.Enter the baud rate, parity, and stop bits, then click the OK button.
It is also possible to enter a
See separate sections below for more details regarding each Modbus protocol.