Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

MECHANICAL INSTALLATION

ELECTRICAL INSTALLATION

For instructions on how to mount the Rosemount 5300/5400 transmitter, refer to the Rosemount 5300 Series Reference Manual (Document No.

00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026).

NOTE

For general electrical installation requirements, including grounding requirements, refer to Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No. 00809-0100-4026).

To connect the Rosemount 5300/5400:

1. Disconnect/shut off the electrical power to transmitter head and then open the instrument cover. Do not remove the cover in an explosive atmosphere with a live circuit.

2.Pull the cable through the cable gland/conduit. For the RS-485 bus, use shielded twisted pair wiring, preferably with an impedance of 120Ω (typically 24 AWG) in order to comply with the EIA-485 standard and EMC regulations. The maximum cable length is 4000 ft/1200 m.

3.Make sure that the transmitter housing is grounded, then connect wires according to Figure 1-2and Table 1-1. Connect the lead that originates from the “A” line from the RS-485 bus to the terminal marked MB, and the lead that originates from the “B” line to the terminal marked MA.

4.If it is the last transmitter on the bus, connect the 120Ω termination resistor.

5.Connect the leads from the positive side of the power supply to the terminal marked POWER +, and the leads from the negative side of the power supply to the terminal marked POWER -. The power supply cables must be suitable for the supply voltage and ambient temperature, and approved for use in hazardous areas, where applicable.

6.Attach and tighten the housing cover. Tighten the cable gland, then plug and seal any unused terminals, and connect the power supply.

1-4

Page 4
Image 4
Emerson 5400, 5300 specifications Mechanical Installation Electrical Installation