Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

SPECIFIC MODBUS HOST CONFIGURATION

The Remote Terminal Unit needs to be configured to communicate and correctly interpret data when reading input registers from the Rosemount 5300/5400 transmitter.

Baud Rate

The specified Baud Rates below are recommendations. If other Baud Rates are used, make sure that the 5300/5400 and the RTU are configured for the same communication speed.

Floating Point Format Code

See Section “Common Modbus Host Configuration” on page 1-25.

RTU Data Type

The RTU Data Type specifies which configuration to use in the RTU in order for the RTU to correctly interpret a floating point number transmitted from the 5300/5400 transmitter with Modbus.

Input Register Base Number

Data registers in the 5300/5400 transmitter with Modbus are numbered exactly as they are transmitted in the Modbus communication. Some RTUs use different naming conventions and to configure the RTU to poll the correct registers from the 5300/5400 Modbus, an Input Register Base Number is stated for each RTU respectively. E.g. if the input register base number is 1 for the RTU, the 5300/5400 Modbus input register 1302 has to be entered in the RTU address as input register 1303.

Emerson Process Management

ROC800 Series

Figure 1-9. Wiring Diagram for

Connecting 5300/5400 Modbus to

Emerson Process Management

ROC800 Series

Table 1-19. Parameter Values (in case of Emerson Process Management ROC800 Series)

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Conversion Code 66

Input Register Base Number

0

 

 

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1300 needs to have 1300 entered as the address.

1-30