Manual Supplement

00809-0500-4530, Rev AA October 2010

Rosemount 5300/5400 Series

Emerson Process Management FloBoss 107

Figure 1-10. Wiring Diagram for Connecting 5300/5400 Modbus to Emerson Process Management FloBoss 107

 

 

 

 

 

FloBoss 107

5300/5400 Modbus

 

 

 

RS-485

MA

 

 

 

 

A

 

 

 

 

MB

 

 

 

 

B

 

 

 

 

POWER +

 

 

 

NC

 

 

 

POWER -

 

 

 

NC

 

 

 

 

 

 

 

 

PWR

 

 

 

 

 

 

 

GND

Power Supply

 

 

 

 

+ 8 to + 30 Vdc

 

 

 

 

(max. rating)

 

 

 

 

GND

 

 

 

 

 

 

 

 

Table 1-20. Parameter Values (in case of Emerson Process Management FloBoss 107)

ABB TotalFlow

Figure 1-11. Wiring diagram for connecting 5300/5400 Modbus to ABB TotalFlow

Table 1-21. Parameter Values (in case of ABB TotalFlow)

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Conversion Code 66

Input Register Base Number

0

 

 

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1300 needs to have 1300 entered as the address.

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

16 Bit Modicon

Input Register Base Number

1

 

 

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc.