Rosemount 5300/5400 Series
Manual Supplement
Thermo Electron Autopilot
Figure 1-12. Wiring Diagram for
Connecting 5300/5400 Modbus to
Thermo Electron Autopilot
5300/5400 Modbus
MA
MB
POWER +
POWER -
AutoPILOT
CEB TB1
1 RX +
2 RX -
Table
Power Supply
+8 to + 30 Vdc (max. rating)
GND
Parameter | Value |
Baud Rate | 9600 |
Floating Point Format Code | 1 |
RTU Data Type | IEEE Flt 2R |
Input Register Base Number | 0 |
|
|
The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1302 entered as the address etc.
Bristol ControlWave Micro
Figure 1-13. Wiring Diagram for Connecting 5300/5400 Modbus to Bristol ControlWave Micro
Table 1-23. Parameter Values (in case of Bristol ControlWave Micro)
| ControlWave Micro | |||
5300/5400 Modbus | Com Port 3 (C3) | |||
MA |
|
|
| |
MB |
| 1 |
| |
POWER + |
| 6 | ||
| 2 | |||
POWER - |
| 7 | ||
TXD- | 3 | |||
| 8 | |||
| TXD+ | 4 | ||
Power Supply | 9 | |||
GND | 5 | |||
+ 8 to + 30 Vdc |
| |||
|
|
| ||
(max. rating) |
| DB9 Male | ||
GND |
| |||
|
|
| ||
Parameter |
| Value |
|
Baud Rate | 9600 |
|
|
Floating Point Format Code | 2 (FC 4) |
|
|
RTU Data Type | |
|
|
Input Register Base Number | 1 |
The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc.