Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

Thermo Electron Autopilot

Figure 1-12. Wiring Diagram for

Connecting 5300/5400 Modbus to

Thermo Electron Autopilot

5300/5400 Modbus

MA

MB

POWER +

POWER -

AutoPILOT

CEB TB1

1 RX +

2 RX -

Table 1-22. Parameter Values (in case of Thermo Electron Autopilot)

Power Supply

+8 to + 30 Vdc (max. rating)

GND

Parameter

Value

Baud Rate

9600

Floating Point Format Code

1

RTU Data Type

IEEE Flt 2R

Input Register Base Number

0

 

 

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1302 entered as the address etc.

Bristol ControlWave Micro

Figure 1-13. Wiring Diagram for Connecting 5300/5400 Modbus to Bristol ControlWave Micro

Table 1-23. Parameter Values (in case of Bristol ControlWave Micro)

 

ControlWave Micro

5300/5400 Modbus

Com Port 3 (C3) RS-485

MA

 

 

 

MB

 

1

 

POWER +

 

6

 

2

POWER -

 

7

TXD-

3

 

8

 

TXD+

4

Power Supply

9

GND

5

+ 8 to + 30 Vdc

 

 

 

 

(max. rating)

 

DB9 Male

GND

 

 

 

 

Parameter

 

Value

 

Baud Rate

9600

 

 

Floating Point Format Code

2 (FC 4)

 

 

RTU Data Type

32-bit registers as 2 16-bit registers

 

 

Input Register Base Number

1

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc.

1-32

Page 32
Image 32