Emerson 5300, 5400 specifications Transmitter Configuration

Models: 5300 5400

1 42
Download 42 pages 48.09 Kb
Page 13
Image 13

Manual Supplement

00809-0500-4530, Rev AA October 2010

Rosemount 5300/5400 Series

TRANSMITTER CONFIGURATION

Configuration data such as Tank Height, Upper Null Zone, dielectric constants, and other basic parameters are configured in the same way as for a standard Rosemount 5300/5400 transmitter. For more information, see the Rosemount 5300 Series Quick Installation Guide (Document No.

00825-0100-4530), and the Rosemount 5400 Series Quick Installation Guide (Document No. 00825-0100-4026).

Make sure that the measurement unit of the Primary Variable (PV) matches the configuration of the Modbus Host since the transmitter output value does not include any information on associated measurement units.

For further information on basic configuration, see the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series Reference Manual (Document No.

00809-0100-4026).

NOTE

The 5300/5400 transmitter with Modbus protocol is configured to HART address 1 at factory. This reduces power consumption by locking the analog output at 4 mA.

1-13

Page 13
Image 13
Emerson 5300, 5400 specifications Transmitter Configuration