Manual Supplement

00809-0500-4530, Rev AA October 2010

Rosemount 5300/5400 Series

Levelmaster Communication Setup

To configure the 5300/5400 transmitter to communicate with the Host in this example, the following text string is written to the HART Slave 1 Message Area:

HMC A44 B4800 PO S2.

HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake.

A44: A indicates that the following number is the new address (address 44). Leading zeroes are not needed.

B4800: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200).

PO: P identifies the following letter as parity type (O = odd, E = even, and N = none).

S2: S indicates that the following figure is the number of stop bits (1 = one, 2 = two).

Only values that differ from the current values need to be included. For example, if only the address is changed, the following text string is written into the 5300/5400 (HART Slave 1) Message Area:

HMC A127,

indicates that 127 is the new address.

The default and configurable parameter values can be found in Table 1-6.

Table 1-6. Levelmaster

Communication Parameters

Parameter

Default value

Configurable value

 

Baud Rate

9600

1200, 2400, 4800, 9600, 19200

 

Start Bits

One

One

 

Data Bits

Seven

Seven, Eight

 

Parity

None

None, Odd, Even

 

Stop Bits

One

One or Two

 

Address

1

1-99

 

 

 

 

To reset the communication parameters to default Levelmaster settings, use the following Modbus Message:

HMC M2

1-17