Manual Supplement

00809-0500-4530, Rev AA October 2010

Rosemount 5300/5400 Series

ScadaPack

Figure 1-14. Wiring Diagram for

Connecting 5300/5400 Modbus to

SCADAPack 32

5300/5400 Modbus

MA

MB

POWER +

POWER -

Power Supply

+ 8 to + 30 Vdc

(max. rating)

REF

SCADAPack32

RS-485 on COM1

1 +5 V

2RX-

3TX-

4 GND

5RX+

6TX+

7Not Used

8Not Used

Table 1-24. Parameter Values (in case of SCADAPack 32)

Kimray DACC 2000/3000

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Floating Point

Input Register Base Number

30001

 

 

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 31303 entered as the address etc.

This table shows input types in Kimray IMI software and the corresponding value. The communication port must be configured to use “Tank Levels” protocol.

Table 1-25. Kimray Input Types and

 

 

 

Corresponding Values

 

 

 

Kimray Inp type

5300/5400 variable

Format

 

 

Tank Level1

PV

ddd.dd.alt. -dd.dd

 

Tank Level2

SV

ddd.dd.alt -dd.dd

 

 

 

 

1-33

Page 33
Image 33
Emerson 5300, 5400 specifications ScadaPack, Kimray Dacc 2000/3000