TROUBLESHOOTING No communication on RS-485 bus (MA, MB)

Check that the cables are connected

Check that PWR+ is connected to + and PWR- is connected to - on the power supply

Make sure the 5300/5400 transmitter is supplied with 8-30 Vdc (max. rating)

Try alternating MA/MB if you are unsure of the polarity

If an RS-485 converter is used, make sure it is properly installed and configured

The last 5300/5400 transmitter may need a terminating 120-Ω resistor connected between MA and MB

No 5300/5400 communication in RRM

Using HART+, HART-

HART modem is not properly connected

Polling address is incorrect in RRM (default 1)

Using MA, MB

See No communication on RS-485 bus

Polling address is incorrect in RRM (default 1)

Cycle the power and wait 20 seconds before polling

No communication with Modbus RTU protocol

See No communication on RS-485 bus

Make sure the “Modbus Communication Protocol Configuration” is done properly

Make sure the Modbus RTU address is unique on the bus

Cycle the power and try to connect

Check the RTU communication settings

No communication with Modbus ASCII protocol

See No communication on RS-485 bus

Make sure the “Modbus Communication Protocol Configuration” is done properly

Make sure the Modbus ASCII address is unique on the bus

Cycle the power, waiting 40 seconds before communication begins

Check the RTU communication settings

No communication with Levelmaster protocol

See No communication on RS-485 bus

Make sure the “Modbus Communication Protocol Configuration” is done properly

Make sure the Levelmaster address is unique on the bus

Cycle the power, waiting 40 seconds before communication begins

Check the RTU communication settings