Installation Instructions

1.1.5Floor Pedestal Installation

Floor pedestals are optional equipment that provide clearance for bottom cable entry or exit for FPC units not installed on raised flooring. The pedestals are adjustable over a limited range (approxi- mately 3-1/2" [89mm]) to allow leveling the FPC and minor adjustments in the unit’s installed height.

! CAUTION

Floor pedestals may be reverse-assembled for shipping. Before installation, the pedestals should be reassembled as shown in Figure 4. When the pedestal is properly assembled, the washer on top of the welded nut provides a bearing surface for the unit’s weight.

1.Insert the pedestal threaded shaft into the pedestal holes in the cabinet base as shown in Figures 1 and 2.

2.Adjust the pedestal height by turning the welded nut/shaft assembly into or out of the pedestal base as required.

3.Lock the height by tightening the jam nut against the pedestal base.

The pedestal may be anchored to the floor by means of the four holes in the base. Locations of floor pedestals are shown in Figures 1 and 2.

Figure 4 Floor pedestal details

3"

Threaded

(76mm)

Shaft

 

Washer

 

Welded Nut

 

Jam Nut

Pedestal

Base

.56" (14mm) diameter mounting holes

2-1/4"

(57mm)

6"

(152mm) square

2-1/4"

(57mm)

2-1/4" 2-1/4"

(57mm) (57mm)