| Installation Instructions | |
Table 4 | Suggested minimum input wire size data (continued) |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Units with Transformers |
| Transformerless Units |
| |||
|
|
|
|
|
|
|
|
|
|
|
kVA |
| Input | Input |
| Input | Suggested Feeder | Full Load | MIB Trip | Suggested Feeder |
|
| Voltage | FLA |
| OPD | Wire Size (AWG) | Amps | Amps | Wire Size (AWG) |
| |
|
| 208 | 427 |
| 600 | (2) 350 kcmil * | 416 | 600 | (2) 350 kcmil * |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 240 | 370 |
| 500 | (2) 250 kcmil * | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 380 | 234 |
| 300 | 350 kcmil | 228 | 300 | 350 kcmil |
|
150 |
|
|
|
|
|
|
|
|
|
|
| 400 | 223 |
| 300 | 350 kcmil | 217 | 300 | 350 kcmil |
| |
|
|
|
|
|
|
|
|
|
|
|
|
| 415 | 215 |
| 300 | 350 kcmil | 209 | 300 | 350 kcmil |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 480 | 185 |
| 250 | 250 kcmil | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 600 | 148 |
| 200 | #3/0 AWG | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 380 | 312 |
| 400 | (2) #3/0 AWG * | 304 | 400 | (2) #3/0 AWG * |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 400 | 297 |
| 400 | (2) #3/0 AWG * | 289 | 400 | (2) #3/0 AWG * |
|
200 |
|
|
|
|
|
|
|
|
|
|
| 415 | 286 |
| 400 | (2) #3/0 AWG * | 278 | 350 | (2) #2/0 AWG * |
| |
|
|
|
|
|
|
|
|
|
|
|
|
| 480 | 247 |
| 350 | (2) #2/0 AWG * | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 600 | 197 |
| 250 | 250 kcmil | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 380 | 352 |
| 450 | (2) #4/0 AWG * | 342 | 450 | (2) #4/0 AWG * |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 400 | 334 |
| 450 | (2) #4/0 AWG * | 325 | 450 | (2) #4/0 AWG * |
|
225 |
|
|
|
|
|
|
|
|
|
|
| 415 | 322 |
| 450 | (2) #4/0 AWG * | 313 | 400 | (2) #3/0 AWG * |
| |
|
|
|
|
|
|
|
|
|
|
|
|
| 480 | 278 |
| 350 | (2) #2/0 AWG * | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 600 | 222 |
| 300 | 350 kcmil | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 380 | 469 |
| 600 | (2) 350 kcmil * | 456 | 600 | (2) 350 kcmil * |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 400 | 446 |
| 600 | (2) 350 kcmil * | 433 | 600 | (2) 350 kcmil * |
|
300 |
|
|
|
|
|
|
|
|
|
|
| 415 | 430 |
| 600 | (2) 350 kcmil * | 417 | 600 | (2) 350 kcmil * |
| |
|
|
|
|
|
|
|
|
|
|
|
|
| 480 | 372 |
| 500 | (2) 250 kcmil * | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 600 | 297 |
| 400 | (2) #3/0 AWG * | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
*Parallel feeders per NEC
OPD = Overcurrent Protection Device inside FPC
Wire sizes based on NEC 2005, Table
1.Main input power feeder should be a dedicated feeder direct from service entrance or other power source possible
2.Ground conductors recommended to be insulated conductors run with power conductors for increased system performance. Ground conductor minimum size per NEC Table
3.Input feeder wire size listed in this table is the minimum feeder size recommended. Larger wire size may be required because of voltage drop or supply overcurrent protection device.
4.For transformerless units with
Table 5 Main input circuit breaker interrupting rating
Standard interrupting rating*
208V | 480V | 600V | |
65 kA | 35 kA | 35 kA | 18 kA |
*Refer to unit specification sheet for units equipped with
13