Emerson FPC Suggested minimum input wire size data continued, Installation Instructions

Models: FPC

1 40
Download 40 pages 27.65 Kb
Page 17
Image 17

 

 

 

 

 

 

 

 

 

Installation Instructions

Table 4

Suggested minimum input wire size data (continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Units with Transformers

 

Transformerless Units

 

 

 

 

 

 

 

 

 

 

 

 

kVA

 

Input

Input

 

Input

Suggested Feeder

Full Load

MIB Trip

Suggested Feeder

 

 

Voltage

FLA

 

OPD

Wire Size (AWG)

Amps

Amps

Wire Size (AWG)

 

 

 

208

427

 

600

(2) 350 kcmil *

416

600

(2) 350 kcmil *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240

370

 

500

(2) 250 kcmil *

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

234

 

300

350 kcmil

228

300

350 kcmil

 

150

 

 

 

 

 

 

 

 

 

 

 

400

223

 

300

350 kcmil

217

300

350 kcmil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

415

215

 

300

350 kcmil

209

300

350 kcmil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

480

185

 

250

250 kcmil

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

148

 

200

#3/0 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

312

 

400

(2) #3/0 AWG *

304

400

(2) #3/0 AWG *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

297

 

400

(2) #3/0 AWG *

289

400

(2) #3/0 AWG *

 

200

 

 

 

 

 

 

 

 

 

 

 

415

286

 

400

(2) #3/0 AWG *

278

350

(2) #2/0 AWG *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

480

247

 

350

(2) #2/0 AWG *

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

197

 

250

250 kcmil

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

352

 

450

(2) #4/0 AWG *

342

450

(2) #4/0 AWG *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

334

 

450

(2) #4/0 AWG *

325

450

(2) #4/0 AWG *

 

225

 

 

 

 

 

 

 

 

 

 

 

415

322

 

450

(2) #4/0 AWG *

313

400

(2) #3/0 AWG *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

480

278

 

350

(2) #2/0 AWG *

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

222

 

300

350 kcmil

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380

469

 

600

(2) 350 kcmil *

456

600

(2) 350 kcmil *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

446

 

600

(2) 350 kcmil *

433

600

(2) 350 kcmil *

 

300

 

 

 

 

 

 

 

 

 

 

 

415

430

 

600

(2) 350 kcmil *

417

600

(2) 350 kcmil *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

480

372

 

500

(2) 250 kcmil *

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

297

 

400

(2) #3/0 AWG *

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

*Parallel feeders per NEC 300-20 and 310-4 FLA = Full Load Amps of Power Center

OPD = Overcurrent Protection Device inside FPC

Wire sizes based on NEC 2005, Table 310-16, using 75°C copper conductor

1.Main input power feeder should be a dedicated feeder direct from service entrance or other power source possible

2.Ground conductors recommended to be insulated conductors run with power conductors for increased system performance. Ground conductor minimum size per NEC Table 250-66. Input power feeder conduit may be used as the safety ground conductor. When conduit is used, adequate electrical continuity must be maintained at conduit connections to enclosures and throughout conduit run.

3.Input feeder wire size listed in this table is the minimum feeder size recommended. Larger wire size may be required because of voltage drop or supply overcurrent protection device.

4.For transformerless units with 3-phase 4W + G input feeder larger wire size may be required because of excessive neutral current (see NEC Table 310-15 note 4: For best performance, the unit should be located as close to load as practical.

Table 5 Main input circuit breaker interrupting rating

Standard interrupting rating*

208V

480V

380-415V

600V

65 kA

35 kA

35 kA

18 kA

*Refer to unit specification sheet for units equipped with non-standard main input breakers.

13

Page 17
Image 17
Emerson FPC user manual Suggested minimum input wire size data continued, Main input circuit breaker interrupting rating