Emerson FPC user manual ASCII interface default parameters, RS-232 ASCII port customer commands

Models: FPC

1 40
Download 40 pages 27.65 Kb
Page 36
Image 36

Operating Instructions

To Set Unit Clock - To set the clock from the unit front panel, simultaneously press the Scan and Hold membrane switches while the time and date screen is displayed on the LCD. A cursor should appear on the selected time and date field. Use the Scan switch to increment the highlighted field and the Hold switch to decrement the highlighted field. Use the Silence push button to select the next time and date field. The time can be displayed in AM/PM or 24-hour format. Simultaneously press the Scan and Hold switches to exit the clock set screen.

RS-232 ASCII Communications Port - Units with power monitoring are equipped with an isolated RS-232 ASCII Communications Port, which allows access to unit monitored parameters and alarm information. The RS-232 port connections are located on the low voltage control terminal strip inside the unit. See typical control wiring in Figure 16.

The ASCII interface default parameters are shown in Table 15.

Table 15 ASCII interface default parameters

Parameter

Default

Interface

RS-232 using EIA voltage levels

 

 

Baud rate

9600

 

 

Parity

None

 

 

Data bits

8

 

 

Stop bits

1

 

 

Terminator

<CR>

 

 

Hand shaking

Not supported

 

 

Structure

Half-duplex

 

 

Echo

OFF

 

 

Change to receive after transmit

1.28 msec

 

 

Minimum delay to transmit after receive

120 µsec

 

 

Maximum response time turn around

300 msec

 

 

Maximum response completion time

500 msec

 

 

Minimum delay between commands

500 msec

 

 

Maximum intercharacter delay

12.5 msec

 

 

The ASCII port uses a Query-Response Format.

Table 17 shows the list of available customer commands. Only one command is serviced at a time. Valid commands are terminated with a carriage return [0Dh]. Commands are accepted in upper or lower case. Responses are in upper case, terminated with a line feed [0Ah] and carriage return [0Dh].

Table 16 RS-232 ASCII port customer commands

Command

Description

Typical Response

 

 

 

Time? <CR>

Unit: Time

03:40:37A<LF><CR>

Date? <CR>

Unit: Date

05-15-97<LF><CR>

UID? <CR>

Unit ID

Unit_No._PDU_21B____<LF><CR>

kVA? <CR>

Nominal kVA

0150<LF><CR>

V? <CR>

Nominal L-L Voltage

0208<LF><CR>

SS1? <CR>

System Information

UNIT_MODEL_NUMBER___SERIAL NUMBER_______

 

(20-character fields

SITE_ID_NUMBER______TAG_NUMBER__________<LF><CR>

 

with comma separators)

 

SA? <CR>

Number of Active Alarms

02, OUTPUT_OVERVOLTAGE__05-15-97,01:25:30A

 

(20-character alarms

OUTPUT_OVERCURRENT__05-15-97,01:27:46A<LF><CR>

 

with time stamp)

 

UPMD?

Monitored Parameters

0484,0485,0483,0210,0212,0211,0121,0122,0121,0068,

<CR>

(32 comma-separated

0085,0120,0131,0018,0030,0092,0033,0600,0038,0041,

 

data fields—see

0043,0549,0632,0599,0000,1528,0018,0019,0020,0045,

 

Table 17 for descriptions

0047,0049,0044<LF><CR>

 

of field positions)

 

32

Page 36
Image 36
Emerson FPC user manual ASCII interface default parameters, RS-232 ASCII port customer commands