Installation Instructions
Figure 3 Recommended minimum service and ventilation clearances
Minimum clearance of 18" (457mm) above unit is recommended for cooling airflow
See Notes 2 and 3.
Front and rear access is required. See Notes 1 and 2.
NOTE
Minimum clearance of 6" (152mm) below unit is recommended for cable entry and exit
1. Service access is required at the front and rear.
2.Service access clearance dimensions: 36" (914mm) for units up to 150V to ground. 42" (1067mm) for units over 150V to ground.
3.Service access is required on the left side, if unit is equipped with Liebert Distribution Monitoring Option.
Table 3 | Liebert FPC heat output | ||
|
|
|
|
|
| Full Load |
|
|
| Heat Output |
|
Unit kVA |
| BTU/Hr (kW) |
|
15 |
| 2,500 (0.73) |
|
|
|
|
|
30 |
| 4,600 (1.35) |
|
|
|
|
|
50 |
| 6,200 (1.82) |
|
|
|
|
|
75 |
| 8,150 (2.39) |
|
|
|
|
|
100 |
| 9,900 (2.90) |
|
|
|
|
|
125 |
| 11,500 (3.37) |
|
|
|
|
|
150 |
| 12,500 (3.66) |
|
|
|
|
|
200 |
| 15,500 (4.54) |
|
|
|
|
|
225 |
| 15,800 (4.63) |
|
|
|
|
|
300 |
| 18,450 (5.40) |
|
|
|
|
|