Installation Instructions

Figure 3 Recommended minimum service and ventilation clearances

Minimum clearance of 18" (457mm) above unit is recommended for cooling airflow

See Notes 2 and 3.

Front and rear access is required. See Notes 1 and 2.

NOTE

Minimum clearance of 6" (152mm) below unit is recommended for cable entry and exit

1. Service access is required at the front and rear.

2.Service access clearance dimensions: 36" (914mm) for units up to 150V to ground. 42" (1067mm) for units over 150V to ground.

3.Service access is required on the left side, if unit is equipped with Liebert Distribution Monitoring Option.

Table 3

Liebert FPC heat output

 

 

 

 

 

 

Full Load

 

 

 

Heat Output

 

Unit kVA

 

BTU/Hr (kW)

 

15

 

2,500 (0.73)

 

 

 

 

 

30

 

4,600 (1.35)

 

 

 

 

 

50

 

6,200 (1.82)

 

 

 

 

 

75

 

8,150 (2.39)

 

 

 

 

 

100

 

9,900 (2.90)

 

 

 

 

 

125

 

11,500 (3.37)

 

 

 

 

 

150

 

12,500 (3.66)

 

 

 

 

 

200

 

15,500 (4.54)

 

 

 

 

 

225

 

15,800 (4.63)

 

 

 

 

 

300

 

18,450 (5.40)

 

 

 

 

 

6

Page 10
Image 10
Emerson user manual Liebert FPC heat output, See Notes 2 Front and rear access is required. See Notes 1