Emerson FPC user manual Suggested minimum input wire size data, Installation Instructions, Input

Models: FPC

1 40
Download 40 pages 27.65 Kb
Page 16
Image 16

Installation Instructions

Table 4 Suggested minimum input wire size data

 

 

 

Units with Transformers

 

Transformerless Units

 

 

 

 

 

 

 

 

 

kVA

Input

Input

 

Input

Suggested Feeder

Full Load

MIB Trip

Suggested Feeder

Voltage

FLA

 

OPD

Wire Size (AWG)

Amps

Amps

Wire Size (AWG)

 

208

43

 

60

#6 AWG

42

60

#6 AWG

 

 

 

 

 

 

 

 

 

 

240

38

 

50

#8 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

380

24

 

30

#10 AWG

23

30

#10 AWG

15

 

 

 

 

 

 

 

 

400

23

 

30

#10 AWG

22

30

#10 AWG

 

 

 

 

 

 

 

 

 

 

415

22

 

30

#10 AWG

21

30

#10 AWG

 

 

 

 

 

 

 

 

 

 

480

19

 

25

#10 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

600

15

 

20

#12 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

208

87

 

110

#2 AWG

83

110

#2 AWG

 

 

 

 

 

 

 

 

 

 

240

75

 

100

#2 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

380

48

 

60

#6 AWG

46

60

#6 AWG

30

 

 

 

 

 

 

 

 

400

45

 

60

#6 AWG

43

60

#6 AWG

 

 

 

 

 

 

 

 

 

 

415

44

 

60

#6 AWG

42

60

#6 AWG

 

 

 

 

 

 

 

 

 

 

480

38

 

50

#8 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

600

30

 

40

#8 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

208

145

 

200

#3/0 AWG

139

175

#2/0 AWG

 

 

 

 

 

 

 

 

 

 

240

125

 

175

#2/0 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

380

79

 

100

#2 AWG

76

100

#2 AWG

50

 

 

 

 

 

 

 

 

400

75

 

100

#2 AWG

72

90

#2 AWG

 

 

 

 

 

 

 

 

 

 

415

72

 

90

#2 AWG

70

90

#2 AWG

 

 

 

 

 

 

 

 

 

 

480

63

 

80

#4 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

600

50

 

70

#4 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

208

215

 

300

350 kcmil

208

300

350 kcmil

 

 

 

 

 

 

 

 

 

 

240

186

 

250

250 kcmil

-

-

-

 

 

 

 

 

 

 

 

 

 

380

118

 

150

#1/0 AWG

114

150

#1/0 AWG

75

 

 

 

 

 

 

 

 

400

112

 

150

#1/0 AWG

108

150

#1/0 AWG

 

 

 

 

 

 

 

 

 

 

415

108

 

150

#1/0 AWG

104

150

#1/0 AWG

 

 

 

 

 

 

 

 

 

 

480

93

 

125

#1 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

600

74

 

100

#2 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

208

286

 

400

(2) #3/0 AWG *

278

350

(2) #2/0 AWG *

 

 

 

 

 

 

 

 

 

 

240

248

 

350

(2) #2/0 AWG *

-

-

-

 

 

 

 

 

 

 

 

 

 

380

157

 

200

#3/0 AWG

152

200

#3/0 AWG

100

 

 

 

 

 

 

 

 

400

149

 

200

#3/0 AWG

144

200

#3/0 AWG

 

 

 

 

 

 

 

 

 

 

415

143

 

200

#3/0 AWG

139

175

#2/0 AWG

 

 

 

 

 

 

 

 

 

 

480

124

 

175

#2/0 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

600

99

 

125

#1 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

208

358

 

450

(2) #4/0 AWG *

347

450

(2) #4/0 AWG *

 

 

 

 

 

 

 

 

 

 

240

310

 

400

(2) #3/0 AWG *

-

-

-

 

 

 

 

 

 

 

 

 

 

380

196

 

250

250 kcmil

190

250

250 kcmil

 

 

 

 

 

 

 

 

 

125

400

186

 

250

250 kcmil

180

225

#4/0 AWG

 

 

 

 

 

 

 

 

 

 

415

179

 

225

#4/0 AWG

174

225

#4/0 AWG

 

 

 

 

 

 

 

 

 

 

480

155

 

200

#3/0 AWG

-

-

-

 

 

 

 

 

 

 

 

 

 

600

124

 

175

#2/0 AWG

-

-

-

 

 

 

 

 

 

 

 

 

12

Page 16
Image 16
Emerson FPC user manual Suggested minimum input wire size data, Installation Instructions, Units with Transformers, Input