Installation
4.5.2Uninterruptible Power
If your XDF is equipped with a UPS, it will require connection to a dedicated electrical circuit. Review the UPS’s user manual before connecting utility power to the unit.
4.5.3MP Advanced Power
MP Advanced Power Strips are available in several power ranges. Consult Table 14 in 12.0 - Specifi- cations or the MP Advanced Power Strip user manual,
4.5.4Condensate Drain Connection
The XDF cooling process removes humidity from the air inside the cabinet. The moisture is collected in a pan and must be removed from the cabinet. The condensate may be fed into a gravity drain or pumped away with an optional,
The
Table 1 Optional condensate pump performance
| Maximum Head, |
Model | feet (m) |
|
|
60Hz | 18 (5.49) |
|
|
50Hz | 14 (4.27) |
|
|
The standard XDF condensate drain is a 1/2" NPT female pipe connector. A
Figure 19 Condensate drain connection and adapter
Condensate Drain Connection 1/2” NPT female connector or 3/4” garden hose with adapter (as shipped)
Bottom Right Rear Corner of XDF
4.6Drycooler Installation—Water/Glycol Cooled Model
For details on installing the drycooler, contact your local Liebert representative.