Specifications

Table 11 Electrical specifications

 

Self- Contained,

Water/Glycol

Electrical Data

Air Cooled XDF

Cooled XDF

 

 

 

Control & Fan Supply

 

 

Voltage

120

120

Ph

1

1

Hz

60

60

Unit FLA

8.3

5.0

Max Fuse or Circuit Breaker Amps

15

15

Min. Supply Circuit Ampacity

9.2

5.2

Receptacle required

NEMA 5-15R

NEMA 5-15R

Compressor Supply

 

 

Voltage

208

208

Ph

3

3

Hz

60

60

Unit FLA

15.7

15.7

Max Fuse or Circuit Breaker Amps

35

35

Min. Supply Circuit Ampacity

19.6

19.6

Receptacle required

NEMA L21-30R

NEMA L21-30R

Condensate Pump Amps (Optional)

0.72

0.72

Table 12 Total heat rejection

Rating Point,

Supply Air

 

 

Ambient

Temperature,

 

Total Heat

°F (°C)

°F (°C)

Load, kW

Rejection, kW

95 (35)

77 (25)

14.1

20

 

 

 

 

50

Page 56
Image 56
Emerson Electrical specifications, Total heat rejection, Self- Contained Water/Glycol Electrical Data Air Cooled XDF