Specifications
Table 11 Electrical specifications
| Self- Contained, | Water/Glycol |
Electrical Data | Air Cooled XDF | Cooled XDF |
|
|
|
Control & Fan Supply |
|
|
Voltage | 120 | 120 |
Ph | 1 | 1 |
Hz | 60 | 60 |
Unit FLA | 8.3 | 5.0 |
Max Fuse or Circuit Breaker Amps | 15 | 15 |
Min. Supply Circuit Ampacity | 9.2 | 5.2 |
Receptacle required | NEMA | NEMA |
Compressor Supply |
|
|
Voltage | 208 | 208 |
Ph | 3 | 3 |
Hz | 60 | 60 |
Unit FLA | 15.7 | 15.7 |
Max Fuse or Circuit Breaker Amps | 35 | 35 |
Min. Supply Circuit Ampacity | 19.6 | 19.6 |
Receptacle required | NEMA | NEMA |
Condensate Pump Amps (Optional) | 0.72 | 0.72 |
Table 12 Total heat rejection
Rating Point, | Supply Air |
|
|
Ambient | Temperature, |
| Total Heat |
°F (°C) | °F (°C) | Load, kW | Rejection, kW |
95 (35) | 77 (25) | 14.1 | 20 |
|
|
|
|
50