Chapter 2 Getting started
Page 2.15
Turn on the
power
4. Turn on the power to the system. The system goes through a Power On Self Test
(POST) routine which takes less than 30 seconds. When it is finished, ignore any
flashing alarm lights which may appear.
Go to the
wizards menu
5. Press the MENU button to go to Page 1 of the Main Menu (if you aren’t there already).
6. Press the DOWN-ARROW button twice to go to Page 3 of the menu.
7. Press the b-button to select “Configure”.
8. Press the a-button twice to go to the wizards menu.
Clear existing
configuration
(This is optional)
9. Press the b-button then the UP-ARROW or DOWN-ARROW button to scroll through the
option list until “Initialise” is shown.
10. Press the b-button to select “Initialise”.
11. Press the d-button to confirm that you want to lose the current configuration.
12. Wait a few seconds until “initialise” on line 2 of the display changes back to
Choose option”.
Select the wizard 13. Press the b-button then the UP-ARROW or DOWN-ARROW button to scroll through
the option list until “Temperature” is shown.
14. Press the b-button to select “Temperature”.
Start of wizard 15. Press the d-button to answer YES to the question “Edit Line Temperature?”.
Choose the
Analogue Input
16. Press the b-button.
17. Press the UP-ARROW button until “Analogue input 1” appears.
18. Press the b-button and then the ENTER button to confirm selection of
“Analogue input 1”.
Choose the type
of Analogue
Input
19. Press the b-button.
20. Press the UP-ARROW button until “PT100 input” appears on line 2.
21. Press the ENTER button twice to select this PRT-type input.
Make the
Analogue Input
Channel “live”
22. Press the d-button.
23. Press the UP-ARROW button so that “Set” has changed to “Live”.
24. Press the ENTER button twice.
Skip over other
questions
25. Press the c-button several times (to answer NO to all further questions) until the wizard
is exited.
View how you
have configured
Line temperature
26. Press the MENU button.
27. Press the d-button and then press the a-button. The display looks similar to that
shown in Figure 2.15 although values shown may vary.
Figure 2.15: Line temperature display
End of Worked Example 5