CHAPTER 1: OVERVIEW

ACCURACY

Measured Parameters

Display Range

Accuracy

 

 

 

Voltage L-N

0 to 9999 kV or scalable

0.1% of reading

Voltage L-L

0 to 9999 V or kV scalable

0.1% of reading

 

 

 

Current

0 to 9999 A or kA

0.1% of reading

 

 

 

+/– Watts

0 to 9999 W, kW, or MW

0.2% of reading

 

 

 

+/– Wh

5 to 8 digits (programmable)

0.2% of reading

 

 

 

+/– vars

0 to 9999 vars, kvars, Mvars

0.2% of reading

 

 

 

+/– varh

5 to 8 digits (programmable)

0.2% of reading

 

 

 

VA

0 to 9999 VA, kVA, MVA

0.2% of reading

 

 

 

VAh

5 to 8 digits (programmable)

0.2% of reading

 

 

 

Power Factor (PF)

±0.5 to 1.0

0.2% of reading

 

 

 

Frequency

45 to 65 Hz

0.01 Hz

 

 

 

% THD

0 to 100%

2.0% F.S.

 

 

 

% Load Bar

10 digit resolution scalable

1 to 120% of reading

 

 

 

NOTE: Typical results are more accurate.

1.4.3 Environmental

 

TEMPERATURE AND HUMIDITY

 

Storage:

–40 to 85°C

Operating:

–30 to 70°C

Humidity:

up to 95% RH, non-condensing

Faceplate rating:

NEMA 12 (water resistant), mounting gasket included

1.4.4 Communications

 

COMMUNICATIONS FORMAT

 

Types:

RS485 port through back plate

 

IrDA port through face plate

COMMUNICATIONS PORTS

 

Protocol:

Modbus RTU, Modbus ASCII, DNP 3.0

Baud rate:

9600 to 57600 bps

Port address:

001 to 247

Data format:

8 bits, no parity

1.4.5 Mechanical Parameters

DIMENSIONS

Size:

4.25" × 4.82" × 4.85" (L × W × H)

 

105.4 mm × 123.2 mm × 123.2 mm (L × W × H)

Mounting:

mounts in 92 mm square DIN or ANSI C39.1 4-inch round

 

cut-out

Weight:

2 pounds / 0.907 kg

Shipping

ships in 6-inch / 152.4 mm cube container

EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE

1–7

Page 13
Image 13
GE EPM 6000 Multi-function Power Metering System instruction manual Environmental, Communications, Mechanical Parameters