CHAPTER 5: COMMUNICATIONS

HEX

DESCRIPTION1

FORMAT

RANGE6

UNITS OR

COMMENTS

# REG

ADDRESS

 

 

 

RESOLUTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIXED DATA SECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Identification Block

 

 

 

 

read-only

 

0000

-

0007

Meter Name

ASCII

16 char

 

none

 

8

0008

-

000F

Meter Serial Number

ASCII

16 char

 

none

 

8

0010

-

0010

Meter Type

UINT16

bit-mapped

 

-------t -----vvv

t = transducer model (1=yes, 0=no),

1

 

vvv = V-switch(1 to 4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0011

-

0012

Firmware Version

ASCII

4 char

 

none

 

2

0013

-

0013

Map Version

UINT16

0 to 65535

 

none

 

1

0014

-

0014

Meter Configuration

UINT16

bit-mapped

 

-------- --ffffff

ffffff = calibration frequency (50 or 60)

1

 

 

 

 

 

 

 

 

 

 

 

 

0015

-

0015

ASIC Version

UINT16

0-65535

 

none

 

1

0016

-

0026

Reserved

 

 

 

 

 

17

0027

-

002E

GE Part Number

ASCII

16 char

 

none

 

8

 

 

 

 

 

 

 

 

Block Size:

47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

METER DATA SECTION2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Primary Readings Block, 6 cycles (IEEE Floating Point)

 

 

read-only

 

0383

-

0384

Watts, 3-Ph total

FLOAT

-9999 M to +9999 M

 

watts

 

2

0385

-

0386

VARs, 3-Ph total

FLOAT

-9999 M to +9999 M

 

VARs

 

2

0387

-

0388

VAs, 3-Ph total

FLOAT

-9999 M to +9999 M

 

VAs

 

2

 

 

 

 

 

 

 

 

Block Size:

6

 

 

 

 

 

 

 

 

 

 

Primary Readings Block, 60 cycles (IEEE Floating Point)

 

 

read-only

 

03E7

-

03E8

Volts A-N

FLOAT

0 to 9999 M

 

volts

 

2

03E9

-

03EA

Volts B-N

FLOAT

0 to 9999 M

 

volts

 

2

03EB

-

03EC

Volts C-N

FLOAT

0 to 9999 M

 

volts

 

2

03ED

-

03EE

Volts A-B

FLOAT

0 to 9999 M

 

volts

 

2

03EF

-

03F0

Volts B-C

FLOAT

0 to 9999 M

 

volts

 

2

03F1

-

03F2

Volts C-A

FLOAT

0 to 9999 M

 

volts

 

2

03F3

-

03F4

Amps A

FLOAT

0 to 9999 M

 

amps

 

2

03F5

-

03F6

Amps B

FLOAT

0 to 9999 M

 

amps

 

2

03F7

-

03F8

Amps C

FLOAT

0 to 9999 M

 

amps

 

2

03F9

-

03FA

Watts, 3-Ph total

FLOAT

-9999 M to +9999 M

 

watts

 

2

03FB

-

03FC

VARs, 3-Ph total

FLOAT

-9999 M to +9999 M

 

VARs

 

2

03FD

-

03FE

VAs, 3-Ph total

FLOAT

-9999 M to +9999 M

 

VAs

 

2

03FF

-

0400

Power Factor, 3-Ph total

FLOAT

-1.00 to +1.00

 

none

 

2

0401

-

0402

Frequency

FLOAT

0 to 65.00

 

Hz

 

2

0403

-

0404

Neutral Current

FLOAT

0 to 9999 M

 

amps

 

2

 

 

 

 

 

 

 

 

Block Size:

30

 

 

 

 

 

 

 

 

 

 

Primary Energy Block

 

 

 

 

read-only

 

044B

-

044C

W-hours, Received

SINT32

0 to 99999999 or

0 to

Wh per energy format

* Wh received & delivered always

2

 

 

 

 

 

 

-99999999

 

 

have opposite signs

 

044D

-

044E

W-hours, Delivered

SINT32

0 to 99999999 or

0 to

Wh per energy format

* Wh received is positive for "view as

2

 

 

 

 

 

 

-99999999

 

 

load", delivered is positive for "view as

 

 

 

 

 

 

 

 

generator"

 

044F

-

0450

W-hours, Net

SINT32

-99999999 to 99999999

Wh per energy format

2

 

 

 

 

 

 

 

 

* 5 to 8 digits

 

0451

-

0452

W-hours, Total

SINT32

0 to 99999999

 

Wh per energy format

2

0453

-

0454

VAR-hours, Positive

SINT32

0 to 99999999

 

VARh per energy format

* decimal point implied, per energy

2

 

format

 

 

 

 

 

 

 

 

 

* resolution of digit before decimal

 

0455

-

0456

VAR-hours, Negative

SINT32

0 to -99999999

 

VARh per energy format

2

 

 

 

 

 

 

 

 

point = units, kilo, or mega, per energy

 

0457

-

0458

VAR-hours, Net

SINT32

-99999999 to 99999999

VARh per energy format

format

2

5–2

EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE

Page 72
Image 72
GE EPM 6000 Multi-function Power Metering System instruction manual Hex