5–4 EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
CHAPTER 5: COMMUNICATIONS
0C2F - 0C30 Positive VARs, 3-Ph,
Maximum Avg Demand FLOAT 0 to +9999 M VARs 2
0C31 - 0C32 Negative Watts, 3-Ph,
Maximum Avg Demand FLOAT 0 to +9999 M watts 2
0C33 - 0C34 Negative VARs, 3-Ph,
Maximum Avg Demand FLOAT 0 to +9999 M VARs 2
0C35 - 0C36 VAs, 3-Ph, Maximum Avg
Demand FLOAT -9999 M to +9999 M VAs 2
0C37 - 0C38
Positive Power Factor, 3-
Ph, Maximum Avg
Demand FLOAT -1.00 to +1.00 none 2
0C39 - 0C3A Negative Power Factor, 3-
Ph, Maximum Avg
Demand
FLOAT -1.00 to +1.00 none 2
0C3B - 0C3C Frequency, Maximum FLOAT 0 to 65.00 Hz 2
Block Size: 34
THD Block7, 13 read-only
0F9F - 0F9F Volts A-N, %THD UINT16 0 to 9999, or 65535 0.1% 1
0FA0 - 0FA0 Volts B-N, %THD UINT16 0 to 9999, or 65535 0.1% 1
0FA1 - 0FA1 Volts C-N, %THD UINT16 0 to 9999, or 65535 0.1% 1
0FA2 - 0FA2 Amps A, %THD UINT16 0 to 9999, or 65535 0.1% 1
0FA3 - 0FA3 Amps B, %THD UINT16 0 to 9999, or 65535 0.1% 1
0FA4 - 0FA4 Amps C, %THD UINT16 0 to 9999, or 65535 0.1% 1
0FA5 - 0FA5 Phase A Current 0th
harmonic magnitude UINT16 0 to 65535 none 1
0FA6 - 0FA6 Phase A Current 1st
harmonic magnitude UINT16 0 to 65535 none 1
0FA7 - 0FA7 Phase A Current 2nd
harmonic magnitude UINT16 0 to 65535 none 1
0FA8 - 0FA8 Phase A Current 3rd
harmonic magnitude UINT16 0 to 65535 none 1
0FA9 - 0FA9 Phase A Current 4th
harmonic magnitude UINT16 0 to 65535 none 1
0FAA - 0FAA Phase A Current 5th
harmonic magnitude UINT16 0 to 65535 none 1
0FAB - 0FAB Phase A Current 6th
harmonic magnitude UINT16 0 to 65535 none 1
0FAC - 0FAC Phase A Current 7th
harmonic magnitude UINT16 0 to 65535 none 1
0FAD - 0FAD Phase A Voltage 0th
harmonic magnitude UINT16 0 to 65535 none 1
0FAE - 0FAE Phase A Voltage 1st
harmonic magnitude UINT16 0 to 65535 none 1
0FAF - 0FAF Phase A Voltage 2nd
harmonic magnitude UINT16 0 to 65535 none 1
0FB0 - 0FB0 Phase A Voltage 3rd
harmonic magnitude UINT16 0 to 65535 none 1
0FB1 - 0FB8 Phase B Current same as Phase A Current 0th to 7th harmonic magnitudes 8
0FB9 - 0FBC Phase B Voltage same as Phase A Voltage 0th to 3rd harmonic magnitudes 4
0FBD - 0FC4 Phase C Current same as Phase A Current 0th to 7th harmonic magnitudes 8
0FC5 - 0FC8 Phase C Voltage same as Phase A Voltage 0th to 3rd harmonic magnitudes 4
Block Size: 42
Phase Angle Block14 read-only
1003 - 1003 Phase A Current SINT16 -1800 to +1800 0.1 degree 1
1004 - 1004 Phase B Current SINT16 -1800 to +1800 0.1 degree 1
1005 - 1005 Phase C Current SINT16 -1800 to +1800 0.1 degree 1
1006 - 1006 Angle, Volts A-B SINT16 -1800 to +1800 0.1 degree 1
1007 - 1007 Angle, Volts B-C SINT16 -1800 to +1800 0.1 degree 1
1008 - 1008 Angle, Volts C-A SINT16 -1800 to +1800 0.1 degree 1
Block Size: 6
HEX
ADDRESS DESCRIPTION1FORMAT RANGE6UNITS OR
RESOLUTION COMMENTS # REG