CHAPTER 5: COMMUNICATIONS

 

HEX

DESCRIPTION1

FORMAT

RANGE6

UNITS OR

COMMENTS

# REG

ADDRESS

 

 

 

RESOLUTION

 

 

 

 

 

 

 

 

 

 

 

0C2F

-

0C30

Positive VARs, 3-Ph,

FLOAT

0 to +9999 M

VARs

 

2

 

 

 

Maximum Avg Demand

 

 

 

 

 

0C31

-

0C32

Negative Watts, 3-Ph,

FLOAT

0 to +9999 M

watts

 

2

 

 

 

Maximum Avg Demand

 

 

 

 

 

0C33

-

0C34

Negative VARs, 3-Ph,

FLOAT

0 to +9999 M

VARs

 

2

 

 

 

Maximum Avg Demand

 

 

 

 

 

0C35

-

0C36

VAs, 3-Ph, Maximum Avg

FLOAT

-9999 M to +9999 M

VAs

 

2

 

 

 

Demand

 

 

 

 

 

0C37

-

0C38

Positive Power Factor, 3-

FLOAT

-1.00 to +1.00

none

 

2

Ph, Maximum Avg

 

 

 

 

 

Demand

 

 

 

 

 

 

 

 

Negative Power Factor, 3-

 

 

 

 

2

0C39

-

0C3A

Ph, Maximum Avg

FLOAT

-1.00 to +1.00

none

 

 

 

 

 

Demand

 

 

 

 

 

0C3B

-

0C3C

Frequency, Maximum

FLOAT

0 to 65.00

Hz

 

2

 

 

 

 

 

 

 

Block Size:

34

 

 

 

 

 

 

 

 

 

THD Block7,

13

 

 

 

read-only

 

0F9F

-

0F9F

Volts A-N, %THD

UINT16

0 to 9999, or 65535

0.1%

 

1

0FA0

-

0FA0

Volts B-N, %THD

UINT16

0 to 9999, or 65535

0.1%

 

1

0FA1

-

0FA1

Volts C-N, %THD

UINT16

0 to 9999, or 65535

0.1%

 

1

0FA2

-

0FA2

Amps A, %THD

UINT16

0 to 9999, or 65535

0.1%

 

1

0FA3

-

0FA3

Amps B, %THD

UINT16

0 to 9999, or 65535

0.1%

 

1

0FA4

-

0FA4

Amps C, %THD

UINT16

0 to 9999, or 65535

0.1%

 

1

0FA5

-

0FA5

Phase A Current 0th

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FA6

-

0FA6

Phase A Current 1st

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FA7

-

0FA7

Phase A Current 2nd

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FA8

-

0FA8

Phase A Current 3rd

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FA9

-

0FA9

Phase A Current 4th

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FAA

-

0FAA

Phase A Current 5th

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FAB

-

0FAB

Phase A Current 6th

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FAC

-

0FAC

Phase A Current 7th

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FAD

-

0FAD

Phase A Voltage 0th

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FAE

-

0FAE

Phase A Voltage 1st

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FAF

-

0FAF

Phase A Voltage 2nd

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FB0

-

0FB0

Phase A Voltage 3rd

UINT16

0 to 65535

none

 

1

 

 

 

harmonic magnitude

 

 

 

 

 

0FB1

-

0FB8

Phase B Current

same as Phase A Current 0th to 7th harmonic magnitudes

 

8

0FB9

-

0FBC

Phase B Voltage

same as Phase A Voltage 0th to 3rd harmonic magnitudes

 

4

0FBD

-

0FC4

Phase C Current

same as Phase A Current 0th to 7th harmonic magnitudes

 

8

0FC5

-

0FC8

Phase C Voltage

same as Phase A Voltage 0th to 3rd harmonic magnitudes

 

4

 

 

 

 

 

 

 

Block Size:

42

 

 

 

 

 

 

 

 

 

Phase Angle

Block14

 

 

 

read-only

 

1003

-

1003

Phase A Current

SINT16

-1800 to +1800

0.1 degree

 

1

1004

-

1004

Phase B Current

SINT16

-1800 to +1800

0.1 degree

 

1

1005

-

1005

Phase C Current

SINT16

-1800 to +1800

0.1 degree

 

1

1006

-

1006

Angle, Volts A-B

SINT16

-1800 to +1800

0.1 degree

 

1

1007

-

1007

Angle, Volts B-C

SINT16

-1800 to +1800

0.1 degree

 

1

1008

-

1008

Angle, Volts C-A

SINT16

-1800 to +1800

0.1 degree

 

1

 

 

 

 

 

 

 

Block Size:

6

 

 

 

 

 

 

 

 

 

5–4

EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE

Page 74
Image 74
GE EPM 6000 Multi-function Power Metering System instruction manual THD Block7