CHAPTER 5: COMMUNICATIONS

14.All 3 voltage angles are measured for Wye and Delta hookups. For 2.5 Element, Vac is measured and Vab & Vbc are calculated. If a voltage phase is missing, the two voltage angles in which it participates are set to zero. A and C phase current angles are measured for all hookups. B phase current angle is measured for Wye and is zero for other hookups. If a voltage phase is missing, its current angle is zero.

5.1.4Modbus Memory Map Data Formats

The date format codes indicated in the Format column of the Modbus memory map are described below:

ASCII: ASCII characters packed 2 per register in high, low order and without any termination characters. For example, "Shark100" would be 4 registers containing 0x5378, 0x6172, 0x6B31, 0x3030.

SINT16 / UINT16: 16-bit signed / unsigned integer.

SINT32 / UINT32: 32-bit signed / unsigned integer spanning 2 registers. The lower-addressed register is the high order half.

FLOAT: 32-bit IEEE floating point number spanning 2 registers. The lower-addressed register is the high order half (i.e., contains the exponent).

EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE

5–9

Page 79
Image 79
GE EPM 6000 Multi-function Power Metering System instruction manual Modbus Memory Map Data Formats