GE EPM 6000 instruction manual 4 32-Bit Binary Counter Without Flag Object 20, Variation

Models: EPM 6000 EPM 6000 Multi-function Power Metering System

1 100
Download 100 pages 59.45 Kb
Page 86
Image 86

CHAPTER 5: COMMUNICATIONS

Change to Modbus RTU Protocol (point 1): EPM 6000 meters are capable of switching from the DNP Protocol to the Modbus RTU Protocol. This enables the user to update the device profile of the meter. This does not change the protocol setting, as a reset returns the meter back to DNP.

The Direct Operate - No Acknowledge (function 6) function will operate only with the settings of Pulsed ON (Code = 1 of the Control Code field) once (Count = 01h) for ON 1 ms and OFF 0 ms.

5.4.432-Bit Binary Counter Without Flag (Object 20, Variation 4)

The counters support the Read function (function 1). A read request for Variation 0 will be responded to with Variation 4.

Counters are used to communicate the hour readings measured by the EPM 6000 meter. Refer to DNP Point Mapping on page 5–10 for details. These readings may be cleared by using the Control Relay Output Block.

5.4.516-Bit Analog Input Without Flag (Object 30, Variation 5)

The analog inputs support the Read function (function 1). A read request for Variation 0 will be responded to with Variation 5.

Refer to DNP Point Mapping on page 5–10 for details on the data measured by the analog inputs.

Health Check (point 0): The health check point indicates problems detected by the EPM 6000. A value of zero (0000h) indicates the meter does not detect a problem; non- zero values indicate a detected anomaly.

Phase-to-Neutral Voltages (points 1 to 3): These points are formatted as two's complement fractions. They represent a fraction of a 150 V secondary input. Inputs greater than 150 V secondary will be pinned at 150 V secondary.

Phase-to-Phase Voltages (points 4 to 6): These points are formatted as two's complement fractions. They represent a fraction of a 300 V secondary input. Inputs greater than 300 V secondary will be pinned at 300 V secondary.

Phase Currents (points 7 to 9): These points are formatted as two's complement fractions. They represent a fraction of a 10 A secondary input. Inputs greater than 10 A secondary will be pinned at 10 A secondary.

Total Real and Reactive Power (points 10 and 11): These points are formatted as two's complement fractions. They represent a fraction of 4500 W secondary in normal operation or 3000 W secondary in open delta operation. Inputs above/below ±4500 or ±3000 W secondary will be pinned at ±4500 or ±3000 W secondary, respectively.

Total Apparent Power (point 12): This point is formatted as a two's complement fraction. It represents a fraction of 4500 W secondary in normal operation or 3000 W secondary in open delta operation. Inputs above/below ±4500 or ±3000 W secondary will be pinned at ±4500 or ±3000 W secondary, respectively.

Power Factor (point 13): This point is formatted as a two's complement integer. It represents power factors from –1.000 (0FC18h) to +1.000 (003E8h). When in open delta operation, the total power factor (point 13) is always zero.

5–16

EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE

Page 86
Image 86
GE EPM 6000 Multi-function Power Metering System 4 32-Bit Binary Counter Without Flag Object 20, Variation