CHAPTER 4: USING THE METER

ZPress ENTER again to select the to Ct-S(CT scaling) value.

The Ct-Svalue can be “1”, “10”, or “100”. Refer to Programming the Configuration Mode Screens on page 4–10 for instructions on changing values.

The value for amps is a product of the Ct-nand the Ct-Svalues.

Example settings for the Ct-Svalue are shown below:

200/5 A: set the Ct-nvalue for “200” and the Ct-Svalue for “1”

800/5 A: set the Ct-nvalue for “800” and the Ct-Svalue for “1”

2000/5 A: set the Ct-nvalue for “2000” and the Ct-Svalue for “1”.

10000/5 A: set the Ct-nvalue for “1000” and the Ct-Svalue for “10”.

ZPress ENTER to scroll through the other CFG parameters. Pressing DOWN or RIGHT displays the password screen (see Reset Mode and Password Entry on page 4–6 for details).

ZPress MENU to return to the main configuration menu.

Ct-nand Ct-Sare dictated by primary current. Ct-dis secondary current.

4.3.5Configuring the PT Setting

Use the following procedure to program the PT setting.

ZPush the DOWN Button to scroll through the configuration mode parameters.

ZPress ENTER when Pt is the active parameter (i.e. it is in the “A” screen and flashing).

4–12

EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE

Page 64