CHAPTER 3: INSTALLATION
3.2Electrical Installation
3.2.1 Installation Considerations
Installation of the EPM 6000 Power Metering System must be performed by only qualified personnel who follow standard safety precautions during all procedures. Those personnel should have appropriate training and experience with high voltage devices. Appropriate safety gloves, safety glasses and protective clothing is recommended.
During normal operation of the EPM 6000, dangerous voltages flow through many parts of the meter, including: Terminals and any connected CTs (current transformers) and PTs (potential transformers), all input/output modules and their circuits. All primary and secondary circuits can, at times, produce lethal voltages and currents. Avoid contact with any
Do not use the meter or any I/O output device for primary protection or in an energy- limiting capacity. The meter can only be used as secondary protection. Do not use the meter for applications where failure of the meter may cause harm or death. Do not use the meter for any application where there may be a risk of fire.
All meter terminals should be inaccessible after installation.
Do not apply more than the maximum voltage the meter or any attached device can withstand. Refer to meter and/or device labels and to the Specifications for all devices before applying voltages. Do not
GE recommends the use of shorting blocks and fuses for voltage leads and power supply to prevent hazardous voltage conditions or damage to CTs, if the meter needs to be removed from service. CT grounding is optional.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
There is no required preventive maintenance or inspection necessary for safety. however, any repair or maintenance should be performed by the factory.
DISCONNECT DEVICE: The following part is considered the equipment disconnect device.
Aswitch or
EPM 6000 |