GE Motor Protection System Run 2 to Run 1 delay between forward and reverse or between speeds

Models: LM10 Motor Protection System

1 106
Download 106 pages 52.19 Kb
Page 28
Image 28

PDU SCREENS AND MENUS

CHAPTER 3: INTERFACE

Run 2 to Run 1 (delay between forward and reverse or between speeds)

Other Settings Sub-menu: The Other Settings menu is used to enable/disable the

following: under/overvoltage, maintained vs. momentary switches, auto restart, DeviceNet fault, and 50 vs. 60 Hz system. It is also used to select the data grouping which is read through DeviceNet polling and to reset elapsed time meter. See Chapter 4 for details.

Auxiliary Relay Faults Sub-menu: The auxiliary or programmable relay can be

triggered upon any or all of the following fault conditions: overcurrent, jam, stall, current unbalance, auxiliary sense fault, load loss, power failure, DeviceNet fault, and under/overvoltage.

Passcode, Login Screen: The unit has three passcode levels – User, Configurator, and Calibrator (shown as "change" on the PDU display). The default condition is User mode. It is necessary to login as Configurator in order to change any parameters. The unit is not meant for field calibration, therefore Calibration mode shall not be discussed in this Guide.

To enter a passcode press Config. and scroll down to the Pass Code field. Press enter to select, then use the up/down arrows to scroll to Config: press enter again to login. An incorrect passcode will force the login back to User.

The default Configurator passcode is “0” and can only be changed when in the Config mode. The menu item to change the passcode will become active after a successful login attempt. The Pass Code is a numeric value between 0 and 65535.

Run Operations Screen: Press in Config. Mode and scroll down to Run Operation, this screen allows control of the Run, Stop, and Reset commands via the PDU. It may be used for test purposes.

Restore Factory Configuration Screen: This screen, available only to Configurator or higher login, resets all parameters to factory defaults. The PDU will prompt the user to confirm the request prior to resetting parameters. Default settings are listed in Table 3 Configuration Parameters.

3–22

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

Page 28
Image 28
GE Motor Protection System, LM10 instruction manual Run 2 to Run 1 delay between forward and reverse or between speeds