GE LM10, Motor Protection System Extension Object, UINT = 16-bit unsigned integer

Models: LM10 Motor Protection System

1 106
Download 106 pages 52.19 Kb
Page 61
Image 61
UINT = 16-bit unsigned integer

CHAPTER 5: COMMUNICATIONSDEVICENET OPERATIONS

Overload Object, Class Code 0x2C, Instance 1:

Attribute

Access

Name/Description

Data Type

Value

 

 

 

 

 

3

Get

FLA

INT

---

 

 

 

 

 

4

Get

Trip Class

USINT

---

 

 

 

 

 

5

Get

Average Current

INT

---

 

 

 

 

 

6

Get

Phase Unbalance

USINT

---

 

 

 

 

 

8

Get

Current Phase A

INT

---

 

 

 

 

 

9

Get

Current Phase B

INT

---

 

 

 

 

 

10

Get

Current Phase C

INT

---

 

 

 

 

 

11

Get

Ground Current

INT

---

 

 

 

 

 

12

Get

Current Scale (fixed at 100 mA)

SINT

1

 

 

 

 

 

UINT = 16-bit unsigned integer

5.1.10 Extension Object

The extension handler object manages the access to settings and parameters not provided for in the standard device type 0x16. It has one instance. It uses instance attributes for all of its functions and data.

Data present in class 0x64 is accessed via explicit messaging.

Extension object, class code 0x64, Services:

Code

Name and Description of Services Available to this Object

 

 

0x0E

Get_Attribute_Single: Returns the contents of the given attribute.

 

 

0x10

Set_Attribute_Single: Sets the contents of the given attribute

 

 

0x32

History, read data from active and history records

 

 

0x33

Login, user level

 

 

0x4A

Call, process function operation

 

 

Extension object, Class Code 0x64, attributes:

Attribute

Access

Name/Description

Data

Value

 

 

 

 

 

none

---

---

---

---

 

 

 

 

 

Extension object, class code 0x64, instance 1:

Attribute

Access

Name/Description

Data Type

Value

 

 

 

 

 

0x00

Get

Series and model

BYTE [2]

 

 

 

 

 

 

0x01

Get

Version and revision

BYTE [2]

 

 

 

 

 

 

0x02

Get/set

User setting, FLA, Run 1, (word)

F1

0.1 A

 

 

 

 

 

0x03

Get/set

User setting, FLA, Run 2, (word)

F1

0.1 A

 

 

 

 

 

0x04

Get/set

User setting, Run 1 ground fault

F2

Trip, Time

 

 

 

 

 

0x05

Get/set

User setting, Run 2 ground fault

F2

Trip, Time

 

 

 

 

 

0x06

Get/set

User setting, Run 1, jam

F3

Trip, Time

 

 

 

 

 

0x07

Get/set

User setting, Run 2, jam

F3

Trip, Time

 

 

 

 

 

0x08

Get/set

User setting, Run 1, stall

F4

Trip, Time

 

 

 

 

 

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

5–55

Page 61
Image 61
GE LM10, Motor Protection System instruction manual Extension Object, UINT = 16-bit unsigned integer