A.3.7 Control and Monitoring of the LM10

LM10 AND ALLEN-BRADLEY SLC500 VIA DEVICENET™

CHAPTER A:

FIGURE A–7: Scanner Module Scanlist

ZClick on Scanlist tab.

The LM10 will be shown under Available Devices.

ZClick the right arrow to move under 'scanlist'. Double-click on LM10-1icon to edit the input/output parameters.

ZSelect Polled and add 1 byte for the Input Size and Output Size. After adding the input/output parameters, you will be prompted for downloading to node 9

A.3.7 Control and Monitoring of the LM10

Polling I/O messaging is for control and monitoring of LM10 relay parameters.

A–20

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL