4.5Motor Start/Stop Logic

LM10 is designed to run in RUN1 and RUN2 mode. However, to illustrate this, only RUN1 mode is described below. The block logic diagram for RUN1 operation is shown in fig. 4-5.

Motor Status: Running 1

The relay can receive the RUN1 Start command as follows:

1.Start command through hardware RUN1 switch input

2.The RUN1 command is selected from the PDU in the configuration mode (used for Test only)

3.Autorestart: the LM10 automatically returns to RUN1 operation after a power loss of up to 4 seconds provided the autorestart setpoint has been enabled and motor was running in RUN1 mode before the power loss

4.A start command is issued remotely through DeviceNet.

A PDU logged-in for configuration will disable run commands from both DeviceNet and hardwired switches.

Motor Stop

Once the motor is in RUN1, it can be stopped as follows:

1.User asserts a hardware STOP switch Input

2.User de-asserts the RUN1 Hardware switch input (Maintained switch setting set to ON)

3.A STOP command issued through a PDU Running Operations command (When RUN1 command issued from PDU)

4.A stop command issued through DeviceNet

5.The relay trips on a protection function operation

6.RUN2 start command issue

7.The relay changed from USER mode to CONFIGURATION mode.

AUX Sense 1 Fault

Aux. Sense 1 fault for open contactor is detected if the main contactor status is still open after 0.1 to 25.0 seconds (user settable) of the RUN1 O/P signal has been issued. The contactor status is fed back to the relay through the AUX. Sense switch Input.

4–42

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

Page 48
Image 48
GE Motor Protection System, LM10 Motor Start/Stop Logic, Motor Status Running, Motor Stop, AUX Sense 1 Fault