4.2.3Language

CHAPTER 4: FUNCTIONALITY

Configuration

Passcode, Login„

Run Operations

Factory default

Configuration

Run Operations „

Factory default

Configuration

Factory deflt „

CONFIGURATION SETTINGS

See page –37.

See page –38.

See page –38.

4.2.3Language

PATH: Configuration Ø ENGLISH/SPANISH

Configuration

 

Configuration

ENGLISH

„

 

ENGLISH

„

CTs & CPTs

 

 

SPANISH

 

Starter Type

 

 

 

 

 

 

 

 

 

Range: SPANISH, ENGLISH

This setting selects the language (either English or Spanish) to display on the PDU interface.

4.2.4CTs and CPTs

PATH: Configuration ØØ CTs & CPTs

Configuration

 

CTs_CPTs

CTs & CPTs „

 

Ctrl Pwr Xformer

Starter Type

 

 

RUN 1 Setup

 

 

 

 

 

 

 

 

 

 

CTs_CPTs

 

 

Cur Xfr / Sensor

 

 

 

 

 

 

 

 

CTs_CPTs

 

 

CT Turns: 1

 

 

 

Range: 200:120; 240:120, 480:120, 600:120, 2400:120, 3000:120, 3300:120, 4200:120, 4800:120, 5400:120, 6000: 120, 7200:120

Range: 27 FLA SenPak, 90 FLA SenPak, 75:5, 100:5, 120:5, 150:5, 200:5, 225:5, 250:5, 300:5, 400:5, 500:5, 600:5, 700:5, 800:5

Range: 1 to 4 in steps of 1

The CT and CPT settings are described below.

Ctrl Pwr Xformer (control power transformer (CPT)): Select a CPT ratio from the choices provided. The default CPT ratio is 240:120.

Cur Xfr / Sensor (current transformer): Select a CT ratio from the choices provided. The first two menu choices refer to sensor packs, while the remaining options are ratios of compatible CTs that might be used with the LM10.

CT Turns: The CT may be configured so that wires are passed through the CT multiple times to increase values. This changes the effective CT ratio. Select a value between 1 and 4 for the number of turns (passes) through the CT.

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL