GE Motor Protection System Configuration Settings, Overview, 1 LM10 Programmable Parameters

Models: LM10 Motor Protection System

1 106
Download 106 pages 52.19 Kb
Page 35
Image 35
4.2Configuration Settings

CHAPTER 4: FUNCTIONALITY

CONFIGURATION SETTINGS

4.2Configuration Settings

4.2.1 Overview

An overview of the LM10 programmable parameters is shown below.

Table 4–1: LM10 Programmable Parameters

Parameter

Range/Options

Default

Reference

 

 

 

 

 

 

 

 

Control power transformer

200:120, 240:120, 480:120, 600:120,

240:120

page 4–31

CPT ratio

2400:120, 3000:120, 3300:120,

 

 

 

4200:120, 4800:120, 5400:120,

 

 

 

6000:120, 7200:120

 

 

 

 

 

 

Current transformer

27 A Sensor Pack, 90 A Sensor Pack,

100:5 Ratio

page 4–31

CT / sensor pack

75:5, 100:5, 150:5, 200:5, 225:5,

 

 

 

250:5, 300:5, 400:5, 500:5, 600:5,

 

 

 

700:5, 800:5

 

 

 

 

 

 

CT turns

1 to 4 in steps of 1

1

page 4–31

 

 

 

 

Starter type

FVNR, FVR, RV, 2S1W, 2S2W, Custom

FVNR

page 4–32

 

 

 

 

FLA (RUN1 and RUN2)

1.2 to 800 A in steps of 0.1

100.0 A

page 4–32

 

 

 

 

Ground fault level

0.4 to 20 A in steps of 0.2 or Off

Off

page 4–32

 

 

 

 

Ground fault timeout

0 to 2.5 seconds in steps of 0.1

0.5 sec.

page 4–32

 

 

 

 

Jam level

100 to 250% of FLA in steps of 1 or

Off

page 4–32

 

Off

 

 

 

 

 

 

Jam timeout

0 to 1000 seconds in steps of 5

120 sec.

page 4–32

 

 

 

 

Stall level

330 to 600% of FLA in steps of 5 or

Off

page 4–32

 

Off

 

 

 

 

 

 

Stall timeout

0 to 30 seconds in steps of 0.5

10 sec.

page 4–32

 

 

 

 

Current unbalance level

2 to 25% of FLA in steps of 1 or Off

Off

page 4–32

 

 

 

 

Current unbalance

0 to 255 seconds in steps of 1

5 sec.

page 4–32

timeout

 

 

 

 

 

 

 

Load loss level

15 to 100% of Full Load in steps of 1

Off

page 4–32

 

or Off

 

 

 

 

 

 

Load loss timeout

0 to 255 seconds in steps of 1

60 sec.

page 4–32

 

 

 

 

Undervoltage

96 V fixed (trip delay time 0.5 sec.)

96 V

page 4–34

 

 

 

 

Overvoltage

140 V fixed (trip delay time 0.5 sec.)

140 V

page 4–34

 

 

 

 

Aux. sense 1 time delay

0.1 to 25.0 sec. in steps of 0.1 for ON

0.4 sec.

page 4–34

Aux. sense 2 time delay

state; 0.0 sec. for Disabled

 

 

 

 

 

 

Run 1 to Run 2 time delay;

0 to 600 seconds in steps of 1

0 sec.

page 4–34

Run 2 to Run 1 time delay

 

 

 

 

 

 

 

Under/overvoltage enable

Off, On

On

page 4–34

 

 

 

 

Maintained input switches

Off = momentary,

Off

page 4–34

 

On = maintained/latched

 

 

 

 

 

 

Auto restart

Off, On

Off

page 4–34

 

 

 

 

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

4–29

Page 35
Image 35
GE Motor Protection System instruction manual Configuration Settings, Overview, 1 LM10 Programmable Parameters