GE LM10 Trip Curves Example, 3 Trip Curve with Jam and Stall Enabled, 4 Cool Down Times

Models: LM10 Motor Protection System

1 106
Download 106 pages 52.19 Kb
Page 33
Image 33
4.1.2Trip Curves Example

CHAPTER 4: FUNCTIONALITY

OVERCURRENT FAULT CONDITIONS

4.1.2Trip Curves Example

A trip curves example with jam and stall enabled is shown below. In this example, we have trip class 20, cold motor, with jam at 150% FLA for 120 seconds, and stall at 600% FLA for 12 seconds.

FIGURE 4–3: Trip Curve with Jam and Stall Enabled

The LM10 will trip on a jam or stall condition if these faults are enabled (see Run 1 and Run 2 Setup on page 4–32). The overcurrent curve cannot be disabled. Therefore, if the jam or stall values are set greater than the time allowed by the standard trip curve, the LM10 will trip before a jam or stall condition can be reached.

Upon an overcurrent, jam, or stall fault, the LM10 forces a cool-down period before the motor may be restarted. The time to reset is calculated as a function of the trip class and percent of full load current (FLA) at the time of the trip. For example, a class 30 motor tripping on a 6 FLA fault will take 9 times longer before it is ready to reset than a class 10 motor tripping on a 2 FLA fault.

FIGURE 4–4: Cool Down Times

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

4–27

Page 33
Image 33
GE LM10, Motor Protection System Trip Curves Example, 3 Trip Curve with Jam and Stall Enabled, 4 Cool Down Times